SubDrive/MonoDrive Connect
Duplex Alternator: Configuration
SubDrive/MonoDrive Connect models support the Duplex
Alternator functionality built-in. This function requires an
appropriate communication cable to be installed between
two SubDrive/MonoDrive Connect units.
Default: Standalone (controllers will operate independently)
Before the Duplex Alternator function will operate, each
drive must be configured individually using the FE Connect
app. The initial lead drive must be configured as Pump 1 and
the initial lag drive must be configured as Pump 2.
When using the built-in Duplex Alternator function with
pressure transducers, the Primary Setpoint of Pump 1
must be set to the desired system pressure. The controller
configured as Pump 1 will automatically control the pressure
set point of the controller configured as Pump 2, setting
it to 5 PSI lower than the primary system set point. When
using the built-in Duplex Alternator function with pressure
switches, the pressure switch connected to the controller
configured as Pump 1 must be set at least 3 PSI higher than
the pressure switch connected to the controller configured
as Pump 2.
NOTE: When using the drawdown function, the same cut-in
pressure must be configured on both controllers.
Duplex Alternator: Switching Interval
When operating two controllers using the Duplex Alternator
function, this parameter sets the accumulated run time
(hours) before the lead and lag systems will alternate roles.
Default: 1 Hour
The Switching Interval time setting on the controller configured as Pump 1
sets the interval time for the overall system.
Once the Duplex Alternator function is configured properly
and operating, the status of the Duplex Alternator system
is shown on the Monitor screen of the app. The roles of the
lead and lag pump can be manually switched by pressing
the Switch Pumps button.
34
All manuals and user guides at all-guides.com
Minimum: 1 Hour
Maximum: 24 Hours
Alternator Configuration
Pump 1 / Pump 2 Selection
Pump 1 Configured
Pump 2 Configured
Alternator Monitor