6 Attachments

Encuentre la causa y repare el problema para mostrar correctamente el estado.
• Asegúrese de que la señal EDM funcione durante el funcionamiento normal.
6
Attachments

UL Standards

The UL/cUL Mark indicates that this product satisfies stringent safety standards. This mark appears on products
in the United States and Canada. It shows UL approval, indicating that it has been determined that the product
complies with safety standards after undergoing strict inspection and assessment. UL-approved parts must be used
for all major components that are built into electrical appliances that obtain UL approval.
This product has been tested in accordance with UL standard UL61800-5-1, and has been verified to be in
compliance with UL standards.
Machines and devices integrated with this product must satisfy the following conditions for compliance with UL
standards.

Area of Use

Installation Environment
Ambient Temperature

Wire the Main Circuit Terminal Block

Wire the main circuit terminal block correctly as specified by the instructions in the manual.
To comply with UL standards on drive models from 2257 and from 4208, use UL-approved closed-loop crimp
terminals. Use the tools recommend by the terminal manufacturer to crimp the closed-loop crimp terminal. Refer
to
Closed-Loop Crimp Terminals on page 122
compliant products).
To select the correct wire gauge, refer to
120
Figure 6.1 UL/cUL Mark
Overvoltage category III and pollution degree 2 or less
UL Type 1 enclosure: -10 °C to +50 °C (14 °F to 122 °F). Derate the output current and output voltage if the drive is installed in
areas with ambient temperatures from +40 °C to +50 °C (104 °F to 122 °F).
IP20 enclosure: -10 °C to +60 °C (14 °F to 140 °F). Derate the output current and output voltage if the drive is installed in areas with
ambient temperatures from +50 °C to +60 °C (122 °F to 140 °F).
for more information about closed-loop crimp terminals (UL-
Main Circuit Wire Gauges and Tightening Torques on page
TOMPYEUOQ2A03C AC Drive Q2A Installation and Operation Instructions