Omron Q2 Serie Instrucciones De Instalación Y Funcionamiento página 16

200 v class 0.55 kw to 110 kw, 400 v class 0.55 kw to 315 kw
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

1 English
No.
(Hex.)
b1-01
Freq. Ref. Sel. 1
(0180)
b1-02
Run Comm. Sel 1
(0181)
b1-03
Stopping Method Selection
(0182)
b1-04
Reverse Operation Selection
(0183)
C1-01
Accel Time 1
(0200)
RUN
C1-02
Decel Time 1
(0201)
RUN
C2-01
Jerk@Start of Accel
(020B)
C2-02
Jerk@End of Accel
(020C)
C2-03
Jerk@Start of Decel
(020D)
C2-04
Jerk@End of Decel
(020E)
C6-01
ND/HD Duty Selection
(0223)
C6-02
Carrier Frequency Selection
(0224)
d1-01 to d1-16
Reference 1 to Reference 16
(0280 - 0291)
RUN
d1-17
Jog Reference
(0292)
RUN
d2-01
FRef Upper Limit
(0289)
d2-02
FRef Lower Limit
(028A)
E1-01
Input AC Supply Voltage
(0300)
E1-04
Max Output Frequency
(0303)
E1-05
Max Output Voltage
(0304)
E1-06
Base Frequency
(0305)
E1-09
Min Output Frequency
(0308)
E2-01
Mot Rated Current (FLA)
(030E)
E2-11
Motor Rated Power (kW)
(0318)
H1-01 - H1-08
DI1 Function Selection to DI8
Function Selection
(0438, 0439, 0400 -
0405)
H2-01
Multi-Function Digital Output 1
(040B)
H2-02
Multi-Function Digital Output 2
(040C)
16
Name
Sets the input method for the frequency reference.
0: Keypad, 1: Analog Input, 2: Modbus, 3: Option PCB, 4: Pulse Train Input
Sets the input method for the Run command.
0: Keypad, 1: Analog Input, 2: Modbus, 3: Option PCB
Sets the method to stop the motor after removing a Run command or entering a Stop command.
0: Ramp->Stop, 1: Coast->Stop, 2: DC Inj->Stop, 3: Timed Coast->Stop, 9: Distance Stop
Sets the reverse operation function. Disable reverse operation in fan or pump applications where reverse rotation is
dangerous.
0: Enabled, 1: Disabled
Sets the length of time to accelerate from zero to maximum output frequency.
Sets the length of time to decelerate from maximum output frequency to zero.
Sets the jerk acceleration time at start.
Sets the jerk acceleration time at completion.
Sets the jerk deceleration time at start.
Sets the jerk deceleration time at completion.
Sets the drive duty rating.
0: HD Rating, 1: ND Rating
Sets the carrier frequency for the transistors in the drive.
1: 2.0 kHz, 2: 5.0 kHz (4.0 kHz for AOLV/PM), 3: 8.0 kHz (6.0 kHz for AOLV/PM),
4: 10.0 kHz (8.0 kHz for AOLV/PM), 5: 12.5 kHz (10.0 kHz for AOLV/PM), 6: 15.0 kHz (12.0 kHz AOLV/PM),
7: Swing PWM 1 (Audible Sound 1), 8: Swing PWM 2 (Audible Sound 2), 9: Swing PWM 3 (Audible Sound 3),
A: Swing PWM 4 (Audible Sound 4), F: User (C6-03 to C6-05)
Sets the frequency reference in the units from o1-03 [FrqDisplay Unit Selection].
Sets the JOG frequency reference in the units from o1-03 [FrqDisplay Unit Selection]. Set H1-xx: MFDI Function
Select = 6 [Jog Reference] to use the Jog frequency reference.
Sets maximum limit for all frequency references. This value is a percentage of E1-04 [Max Output Frequency].
Sets minimum limit for all frequency references. This value is a percentage of E1-04 [Max Output Frequency].
Sets the drive input voltage.
Sets the maximum output frequency for the V/f pattern.
Sets the maximum output voltage for the V/f pattern.
Sets the base frequency for the V/f pattern.
Sets the minimum output frequency for the V/f pattern.
Sets the motor rated current in amps.
Sets the motor rated output in 0.01 kW increments.
Sets the functions for MFDI terminals DI1 to DI8.
Sets the function for MFDO terminal 2NO-2CM.
Sets the function for MFDO terminal 3NO-3CM.
Description
TOMPYEUOQ2A03C AC Drive Q2A Installation and Operation Instructions

Publicidad

Tabla de contenido

Solución de problemas

loading

Productos relacionados para Omron Q2 Serie

Este manual también es adecuado para:

Q2a serieQ2a-a serie

Tabla de contenido