Ce Low Voltage Directive Compliance; Area Of Use; Guarding Against Debris; Connect A Fuse To The Input Side (Primary Side) - Omron Q2 Serie Instrucciones De Instalación Y Funcionamiento

200 v class 0.55 kw to 110 kw, 400 v class 0.55 kw to 315 kw
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

European Directive

CE Low Voltage Directive Compliance

2014/35/EU

EMC Directive

2014/30/EU
Machinery Directive
2006/42/EC
CE Low Voltage Directive Compliance
This product is tested according to IEC/EN 61800-5-1:2007 and complies with the CE Low Voltage Directive.
The following conditions must be satisfied for machines and devices incorporating this product to comply with
the CE Low Voltage Directive.

Area of Use

Install this product in a location with overvoltage category III and pollution degree 2 or less. These standards are
defined by IEC/EN 60664.

Guarding against Debris

When installing IP20 enclosure drives, use an enclosure that does not let unwanted material enter the drive from
above or below.

Connect a Fuse to the Input Side (Primary Side)

The drive circuit protection must comply with IEC/EN 61800-5-1:2007 for protection against a short circuit in the
internal circuitry. Connect a semiconductor protection fuse on the input side for branch circuit protection.
Refer to
Factory Recommended Branch Circuit Protection on page
WARNING
Electrical Shock Hazard. Do not immediately energize the drive or operate peripheral devices after the drive
blows a fuse or trips an RCM/RCD. Wait for the time specified on the warning label at a minimum and make sure that all
indicators are OFF. Then check the wiring and peripheral device ratings to find the cause of the problem. Contact the
manufacturer before energizing the drive or peripheral devices if the cause is not known. Failure to obey can cause death or
serious injury and damage to the drive.
EMC Directive
All drives were tested in accordance with European standard IEC/EN 61800-3:2004/A1:2012, and comply with
the EMC Directive.
Use drives with built-in EMC filters or install external EMC filters to the drive input side to comply with the
EMC Directive.

Install a Drive to Conform to the EMC Directive

Install drives with this procedure to comply with the EMC Directive when the drive is a single unit or installed in
a larger device.
1.
Install the drive on a grounded metal plate.
2.
Wire the drive and motor.
3.
Enable the internal EMC filter.
TOMPYEUOQ2A03C AC Drive Q2A Installation and Operation Instructions
Table 1.5 Harmonized Standard
IEC/EN 61800-5-1:2007
EN 61800-3 2004+A1:2012
• EN ISO 13849-1:2015 (Cat. 3, PL e)
• IEC 62061/A1:2012 (SIL CL 3)
• EN 62061/A1:2013 (SIL CL 3)
• IEC/EN 61800-5-2:2007 (SIL3)
Harmonized Standard
131.
1 English
EN
23