BMP 01-EL1PP _ 1A- _ _ _ _ -00 -P _ _ /P _ _ -S4/P _ _ -S75
Magnetic Field Positioning System
4
Installation and connection (continued)
4.3

Mounting with floating target

For mounting with a floating target, mounting screws are
required (see accessories on page 30).
Distances and tolerances to be observed
To guarantee function, the following distances for the
target must be observed:
BMP
12±2
Fig. 4-11:
Distances and tolerances, shown using an example of a
round magnet target Ø10×10 mm with remanence B
~360 mT
Hole spacing
Hole spacing = Measuring range + 2 mm (hole pattern
tolerance = ±0.05 mm)
Example: Measuring range 128 mm
Hole spacing = 130 mm ±0.05 mm
Direct and inverse mounting
The BMP can be mounted directly (sensing surface
pointing to mounting surface) or inversely.
Fig. 4-12:
Installation with floating target (inverse mounting), axially
polarized target (example, N and S can also be swapped)
12
english
Target
R
S
N
For inverse mounting, a recess for the button
and the LEDs must be provided (for dimensions,
see Fig. 4-13); otherwise, the BMP can only be
configured via IO-Link.
Ø 8
2.7
1.4
6.9
17.8
Fig. 4-13:
Dimensions and distances of the button and LEDs
1. Provide boreholes (distances depend on type; see
Fig. 3-1 on page 7 and Hole spacing on
page 12).
2. Attach the BMP to a surface using mounting screws
(see Accessories on page 30) and a torque of
0.1 Nm.