BMP 01-EL1PP _ 1A- _ _ _ _ -00 -P _ _ /P _ _ -S4/P _ _ -S75
Magnetic Field Positioning System
7
IO-Link interface (continued)
Teach In operation
1. Using Tl Select, select the desired switching signal
(1 to 4)
2. Move the target to the switch-on position.
3. Execute system command Single Value Teach SP1
(0x41) (see System commands on page 20).
4. Move the target to the switch-off position.
5. Execute system command Single Value Teach SP2
(0x42) (see System commands on page 20).
The steps can be checked using parameter
Teach-In Result.
7.5.3

Output configuration

Both outputs of the BMP can be configured.
Index
Subindex
Output Type
1
0x00B4 (180)
2
Tab. 7-10: Configuration of the outputs
7.5.4

Diagnostic suppression

If diagnostic functions are causing problems in the
application, these functions can be suppressed.
For diagnostics events implemented in BMP, see Event list
on page 27.
Index
Subindex
Diagnosis
1
Suppression
Configuration
0x00F8 (248)
2
Tab. 7-11: Diagnostic suppression
24
english
Name
Size
Out 1
1 byte
Out 2
1 byte
Name
Size
Suppression Level
1 byte
PD Invalid Suppression
1 byte
Access
Values
Read/Write 0 = Deactivated
1 = PNP (default)
2 = NPN
3 = Push-Pull
Read/Write 0 = Deactivated
5 = Current 4 to 20 mA
6 = Voltage 0 to 10 V (default)
Access
Values
Read/Write 0 = All events active (default)
1 = Messages suppressed
2 = Messages and warnings suppressed
3 = All events suppressed
Read/Write 0x00 (0) = PD Invalid active
0xFF (255) = PD Invalid suppressed