11.15 - Emergency Opening Command (N.C.) "EMERGENCY MUSHROOM BUTTON"
If parameter Y is set to value 2, input
EMERGENCY
OPENING command, (NORMALLY CLOSED).
The Emergency Opening command results in opening of the door
11.16 - SLOW. PHOTO command (N.C.)
FOTO RALL
The
command results in reopening of the door if in
the closing phase, its immediate slowing down if in the opening
11.17 - Battery
If the battery is present (parameter P = 1), upon start-up and then
every 4 hours the voltage of the same is monitored, temporarily
disconnecting the power supply.
If the battery is faulty, disconnected or completely discharged,
the equipment turns off for a few moments during the test and
then turns on again. This event is automatically stored, and the
11.18 - No mains power supply
If the battery is present, the equipment continues to operate
even during a power failure (signalled with error
supply), according to the methods set by parameter F. The speed
of movements is slightly slowed down. If the mains failure persists
11.19 - Interlock
The interlock function can be enabled.
In this case, once the radar impulse has been received, the door
opens only if the IL.I input is not active, and in turn activates the
IL.O.
The radar pulse received while the IL.I input is active is stored and
executed only when the IL.I input is deactivated.
If the interlock function is disabled, the IL.I input becomes a
CN7 Interlock connection connector
IL.0
IL.I
COM
INT
I
.
becomes the
E04
– No power
Interlock 0
Interlock 1
Common interlock
Interlock function
Port 1
in any condition, including the lock mode and the active STOP
command. As long as it remains active, it does not allow the door
to be closed again.
phase, and as long as it remains active, it does not allow it to be
closed again.
test is no longer repeated, in order to avoid further shutdown of
the equipment every 4 hours. If the battery voltage drops below
23.5 volts, the E05-low battery error is signalled. In this case, the
equipment continues to operate according to the methods set by
parameter G.
and the battery voltage drops below 22 V, the error
depleted is signalled. The door movements are in any case
inhibited.
command for the partial opening of the door.
Select function Y=1 in the 2 control units when the doors must
open alternately.
This function allows the second automatic door to be opened only
when the first automatic door is completely closed and vice-versa,
it is used for the classic thermal break and for safety reasons.
E07
– battery
Port 2
EN
71