Installation
Connecting the PDU
Each model is equipped with one of four different input plugs.
2-1
L15-30P
200–240V
Input
Monitored Models
Plug
PDU3EVN1G60B
IEC 309
60A
(3P+E)
PDU3EVN1H50B
Hubbell
CS8365C
PDU3EVN1L1530B
NEMA
L15-30P
PDU3EVN1L2130B
NEMA
L21-30P
200–240V
Input
Switched Models
Plug
PDU3EVSR1L1530D
NEMA
L15-30P
PDU3EVSR1L2130D
NEMA
L21-30P
PDU3EVSR1H50D
Hubbell
CS8365C
PDU3EVSR1G60
IEC 309
60A
(3P+E)
PDU3EVSR1H50
Hubbell
CS8365C
PDU3EVSR1L1530
NEMA
L15-30P
PDU3EVSR1L2130
NEMA
L21-30P
L21-30P
Hubbell CS8365C
Total
Max Input Amps
Capacity
(Limited by Input
(240V)
Cord and Plug)
14.5kW
35A
14.5kW
35A
10kW
24A
10kW
24A
Total
Max Input Amps
Capacity
(Limited by Input
(240V)
Cord and Plug)
10kW
24A
10kW
24A
14.5kW
35A
14.5kW
35A
14.5kW
35A
10kW
24A
10kW
24A
7
IEC 309 60A Blue
Nominal
Nominal
Input
Output
Output
Voltage(s)
Voltage(s)
Breakers
200-240V
200-240V
3 Double-
Pole 20A
200-240V
200-240V
3 Double-
Pole 20A
200-240V
200-240V
3 Double-
Pole 20A
200-240V
200-240V
3 Double-
Pole 20A
Nominal
Nominal
Input
Output
Output
Voltage(s)
Voltage(s)
Breakers
200-240V
200-240V
3 Double-
Pole 20A
200-240V
200-240V
3 Double-
Pole 20A
200-240V
200-240V
3 Double-
Pole 20A
200-240V
200-240V
3 Double-
Pole 20A
200-240V
200-240V
3 Double-
Pole 20A
200-240V
200-240V
3 Double-
Pole 20A
200-240V
200-240V
3 Double-
Pole 20A
(3P + E)
Cord
Length Outlets
10 ft.
42 C13
(3 m)
6 C19
10 ft.
42 C13
(3 m)
6 C19
10 ft.
42 C13
(3 m)
6 C19
10 ft.
42 C13
(3 m)
6 C19
Cord
Length Outlets
10 ft.
42 C13
(3 m)
10 ft.
42 C13
(3 m)
10 ft.
42 C13
(3 m)
10 ft.
30 C13
(3 m)
6 C19
10 ft.
30 C13
(3 m)
6 C19
10 ft.
30 C13
(3 m)
6 C19
10 ft.
30 C13
(3 m)
6 C19