5
Installation
5.1
Select location
Requirement(s):
ü Technical data and mains data are the same.
1 "4 Technical data" [} 11]
ü Permissible ambient conditions are observed.
ü The product and the charging station are in suf-
ficient proximity to each other, depending on
the length of the charging cable used.
ü The following minimum clearances to other ob-
jects (e.g. walls) must be complied with:
n Distance to left and right: 300 mm
n Distance above: 300 mm
5.1.1 Permissible ambient conditions
DANGER
Risk of explosion and fire
If the product is operated in potentially explosive
areas (ex areas), explosive substances may be ig-
nited by sparking of product components. There is
a risk of explosion and fire.
u Do not use the product in potentially explosive
atmospheres (e.g. gas filling stations).
ATTENTION
Material damage due to unsuitable ambient con-
ditions
Unsuitable ambient conditions can damage the
product.
u Protect the product from a direct water jet.
u Avoid direct sunlight.
u Ensure adequate ventilation of the product. Ad-
here to minimum distances.
u Keep the product away from heat sources.
u Avoid large temperature fluctuations.
Permissible ambient conditions
Ambient temperature [°C]
14
5.2
5.2.1 Upstream electrical installation
Fire hazard due to overload
If the upstream electrical installation is flawed (e.g.
supply line), there is a fire hazard.
u Design the upstream electrical installation ac-
1 "4 Technical data" [} 11]
u Route the supply line and the control / data
Recommendation for a data line (e. g. connecting to
an external energy meter or energy management
system) can be found in chapter:
1 "5.7 Connecting the data line (Modbus RTU)"
Min.
Max.
-30
+50
Permissible ambient conditions
Average temperature over 24
hours [°C]
Altitude [m above sea level]
Relative humidity (non-con-
densing) [%]
Preparatory work on site
The tasks described in this section may only
be carried out by a qualified electrician.
DANGER
cording to the applicable regulatory standards
and the technical data and configuration of the
product.
When configuring the supply line (cross
section and cable type), give due consider-
ation to the following local conditions,
among others:
n Type of installation
n Cable length
n Clustering of cables
cable, if applicable, to the desired location.
[} 19]
Min.
Max.
+35
2,000
95