100304 - 22-kW HOME STANDBY GENERATOR WITH AXIS CONTROLLER
8. Remove the spark plug and spray fogging oil into the spark
plug hole. Install the spark plug and tighten.
9. Thoroughly wash and wax the exterior of the generator
enclosure. Do not use a pressure washer.
Return to Service after Storage
1. Make sure the utility power to the transfer switch is off.
2. Make sure the generator ON/OFF switch is in the OFF
position.
3. Remove the fuse from the front of the aXis Controller
will disable automatic starting in the event of a power outage.
4. Put the aXis Controller
®
example.
5. Check the engine oil level. Add oil if needed.
6. Recharge the batteries to 100% state of charge. If the
batteries will not fully charge, replace the batteries.
Always connect the positive (+) battery cable first. After the
positive cable is connected, then the negative (-) battery cable
can be attached. This minimizes the possibility of electrical
contact.
7. Connect the positive (+) battery cable to the positive (+)
battery terminal first and then connect the negative battery
cable to the negative (-) battery terminal.
8. Clean and wipe down the generator with mild soap and water.
9. Turn the fuel shutoff valve to the ON position.
10. Press the MAN (Manual) button on the aXis Controller
start and run the HSB. The engine should start. Run the
engine for 15 minutes to allow it to warm up. The fuel system
might require more than one start cycle to fully pressurize the
fuel system for operation.
11. Make sure there are not any active fault codes.
12. Press the OFF button on the aXis Controller
13. Turn the generator ON/OFF switch to the OFF position.
14. Turn on the utility power to the transfer switch. Check the
icons on the aXis Controller
to either MANUAL or AUTO for
WARNING
.
®
.
®
®
. This
®
to
®
33
MAINTENANCE