100304 - 22-kW HOME STANDBY GENERATOR WITH AXIS CONTROLLER
HSB starts, then suddenly stops
1
Check for active fault code.
2
Fuel supply insufficient*
3
Low oil pressure shut down.
4
Generator over loaded.
5
Engine high/over temperature shut down.
No AC output
1
Circuit breaker in "OFF" position
2
Main circuit breaker in "OFF" position.
3
Transfer switch breaker in "OFF" position.
4
Standby breakers set in "OFF" position.
5
Line circuit tripping breaker because of short circuit *
6
Line circuit tripping breaker because of overload *
7
Poor wiring connections*
8
ATS problems*
Reset fault code(s)
There is an exterior warning LED located on the back of the enclosure. This should be checked weekly to make sure there are no active
fault codes.
Maintenance
The maintenance hour meter counts from 100 hours to 0.
1
You need to reset when the hour meter reaches 0.
BATTERY(S) NO OR LOW LEVEL CHARGED, BATTERY(S) DEAD, NEEDS REPLACEMENT, THE EXERCISE TIME MUST BE RESET ONCE
THE BATTERY(S) HAVE BEEN DISCONNECTED.
* *Contact Champion Power Equipment, Technical Service toll free 1-877-338-0999, tech@championpowerequipment.com or your nearest Champion dealer.
www.championpowerequipment.com
®
Identify fault code, correct and reset.
Manometer check, confirm fuel pressure to fuel regulator*.
Check for oil leaks. Check the oil level and add oil if necessary.
Turn off standby circuits for house, reset fault, place unit back into
AUTO mode. Turn on standby circuits for house. If problem returns
contact Champion or Champion service dealer*.
Check all intake and exhaust ventilation around the HSB, remove all
debris. Let HSB sit for 30 minutes to cool down.
Turn on breaker.
Turn on breaker.
Turn on breaker.
Turn on breaker.
Refer to "Resetting the maintenance hour meter" for instructions after
performing maintenance.