Balluff BMD 1H Serie Manual De Instrucciones página 133

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

Failure
Code
Reason
Text mes-
sage
F013
Sensor does not detect an
echo during operation
no measured
Process component or probe
value avail-
contaminated or defective
able
F017
cation
Adjustment
span too small
F025
Index markers are not con-
tinuously rising, for example
Error in the
illogical value pairs
table
F036
Failed or interrupted software
update
No operable
software
F040
Hardware defect
Error in the
electronics
F041
Probe mechanically defec-
tive
Probe loss
F080
General software error
General soft-
ware error
F105
The instrument is still in the
start phase, the measured
Measured
value could not yet be
value is deter-
determined
mined
F113
EMC interference
Transmission error during
Communica-
external communication with
tion error
4-wire power supply unit
F260
Error in the calibration car-
ried out in the factory
Error in the
Error in the EEPROM
calibration
F261
Error during setup
Error when carrying out a
Error in the
reset
instrument
False signal suppression
settings
faulty
This status message is inactive by default. It can be activated by the
user via PACTware/DTM or EDD.
The following table shows the error codes in the status message
"Failure
in mind that some information is only valid for four-wire instruments.
Recti cation
Check for correct mounting
and/or parameter settings
Clean or exchange process
component or probe
-
Change adjustment accord-
ence between min. and max.
Check values of the lineari-
Delete/create a new lineari-
Repeat software update
Check electronics version
Exchanging the electronics
Send instrument for repair
Exchanging the electronics
Send instrument for repair
Check probe and exchange,
if necessary
Disconnect operating voltage Bit 5 of Byte 0 ... 5
Wait for the end of the
switch-on phase
Duration depending on
the version and parameter
adjustment max. 5 min.
Exchange 4-wire power sup-
ply unit or electronics
Exchanging the electronics
Send instrument for repair
Carry out a reset
Repeat setup
9 Diagnostics and servicing
DevSpec State in CMD 48
Bit 0 of Byte 0 ... 5
Bit 1 of Byte 0 ... 5
-
Bit 2 of Byte 0 ... 5
Bit 3 of Byte 0 ... 5
Bit 4 of Byte 0 ... 5
Bit 13 of Byte 0 ... 5
Bit 6 of Byte 0 ... 5
Bit 12 of Byte 0 ... 5
Bit 8 of Byte 0 ... 5
Bit 9 of Byte 0 ... 5
51