Attaching the LDL tank
15 072 99
Installation of the connection line between LDL tank and monitoring space of the tank
For installation, it is recommended that you use the GOK assembly set for the leak
detector, Art. No. 15 072 99.
Connections:
• LDL tank: Male thread G 3/4 according to EN ISO 228-1 and double sleeve G 3/4 (included
with delivery).
• Tank: Generally, a sleeve with a female thread G 1 EN ISO 228.
The following options are available for the connection line:
• Threaded tube according to EN 10255 (DIN 2440), not zinc-plated inside, outside with
surface protection, e.g. dimension R 3/4.
• Copper tube according to EN 1057 or EN 13349 with plastic sheath and isolation part,
recommended in dimension 15 x 1mm.
• Install the isolation part directly on to the tank connection.
• LDL tank installed in the dome: EPDM hose 14 x 3.
Installing the check valve
Tank connection: Generally,a sleeve with female thread G 1 according to EN ISO 228:
The check valve
Install the check valve on the second support of the monitoring space
Distance between outlet of check valve and LDL tank: ≥ 10cm.
The check valve is included in the GOK assembly set for the leak detector,
Art. No. 15 072 99.
part no. 15 071 53 d
Check for completeness and damage.
Define the installation location.
To be attached to a nearby wall, to an intended fittings
cabinet, or to the dome with a tripod made from flat or
angled iron.
Define the installation height for attaching =
installation dimension a + 287.5mm.
Mark the attachment holes horizontally.
Drill the holes for anchors and insert anchors, e.g. S10 x 50 anchors.
Attach the LDL tank with 2 screws, e.g. hexagonal wood screws 8 x 40
steel, zinc-plated according to DIN 571.
The screws and anchors are included in the GOK assembly set for the
leak detector, Art. No. 15 072 99.
must be positioned so that a collection vessel placed below it.
Leak detector type LAG 2000 A
.
17 / 28