Please read this operating manual and the safety data sheet for the leak detector
liquid before you use it for filling purposes!
Filling the leak detector liquid
1.
Determine the volume of the monitoring space for the required volume of leak detector
liquid
– see type label on the tank
2.
Place a collection vessel below the check valve
3.
Open the check valve
4.
Remove the sensor unit
5.
Add leak detector liquid until
6.
Vent the air in the system, if necessary, replenish the leak detector liquid
7.
Close the check valve
8.
Fill leak detector liquid
9.
Check the connection between the fuel tank – LDL tank, include. connections, for leaks.
10. Install the sensor unit
11. Attach a permanent label indicating the leak detector liquid that is used
to the LDL tank as well as an accompanying safety data sheet (SDS), making sure that it
is clearly visible.
Starting up the display unit
The display unit starts operating as soon as the connections have been installed properly
according to "Installing the display unit".
FUNCTION CHECK
Function check of the indicator with the initial start-up
22 / 28
.
.
from the LDL tank
einfüllen it flows from the check valve
.
to the middle of the inspection glass
.
• Green light
• Press
Red light
is triggered OK.
• Press
• Red light
A4 is switched off OK.
• Place a collection vessel below the check valve
• Open the check valve
• Red light
is triggered OK.
• Close the check valve
• Remove the sensor unit
• Fill leak detector liquid middle of the inspection glass
of the LDL tank
• Replace the sensor unit
Red light
A4 is switched of OK.
Leak detector type LAG 2000 A
.
.
A1 is lit OK.
A5 and set to "ON":
A3 is lit and the alarm buzzer A4
A5 again and set to "OFF":
A3 goes out and the alarm buzzer
A3 is lit and the alarm buzzer A4
.
from the LDL tank
.
in the LDL tank
A3 goes out and the alarm buzzer
.
.
of the LDL tank.
.
:
part no. 15 071 53 d
.