Reset unit
DIP switch
Fig. 8
7.2 Function
The reset unit is mounted on the base board and electrically connected to it with a flat
cable. The reset unit is connected to the rechargeable battery via terminals and a
two-core line. In case of a failure of the supply, the rechargeable battery is
electronically switched on automatically after 5 seconds. With DIP switches (5), the
function «Move to the CLOSED or OPEN position» can be selected.
Only EA11: After a power failure, EA11 needs 120 seconds, until the input signal will
be responded to again.
Setting DIP switch
ON = Actuator moves to the OPEN position
OFF = Actuator moves to the CLOSED position
Charge the rechargeable battery completely, before use. Full recharging takes
approx. 24 hours without running motor.
7.3 Assembly
Disconnect the actuator from the supply voltage.
Take the board out of its packaging and check for damages.
Screw three spacer bolts 1 into installation domes and tighten by hand.
Fasten board 3 to the spacer bolts with screws 2 and washers.
Plug the flat cable into plug X1 6.
Connect the supply voltage.
Rechargeable battery
Connect the battery via the second plug or cable gland to terminals 16 and 17.
Recommendation 2 x 1.5 mm
Observe the polarity, see wiring diagram.
Charge the battery for at least 24 hours.
62
2
.
Accessories for electrical actuators