Position signalization
Accessories for electrical actuators
For new learning run 360 °:
Disconnect the actuator from the valve, to avoid damage to the valve.
Before doing the learning run, set the jumper so it connects the two pins.
Perform the learning run.
Put the jumper into the original position.
Mount the actuator.
9
Fig. 11
If the position signalization is combined with the monitoring print,
the output signal 4 – 20 mA can be processed on the terminals (18 and 19) 9 on the
board of the monitoring print. (4 mA > CLOSED / 20 mA > OPEN).
If the position signalization is connected to the positioner,
the positioner will process the signal.
66