Middle position
15.3 Assembly
Spacer
Switching cam 4
Switching cam 3
Fig. 28
Disconnect the actuator from the supply voltage.
Remove the housing cover from the actuator.
Remove the screws of limit switches S1 and S2.
Remove the optical position indicator from the shaft.
Push switching cam 3 and switching cam 4 on the shaft.
Push the spacer on the shaft.
Set limit switches S3 and S4 for the middle position on the already mounted limit
switches S1 and S2 and screw tight, see Fig. 28
Plug the red plug of limit switches S3 and S4 on the four-pole slot 3. Make sure
that the multipoint socket connector of the plug fits into the socket board of the
four-pole plug.
88
Accessories for electrical actuators
Limit switch S4
Limit switch S3
3