Positioner PE25
Terminal assignment positioner
199 190 100
20
SET value input current
21
SET value input voltage/frequency
22
-
23
SET value input ground
30
Position signalization signal
31
Position signalization ground
The position signal at terminals 30, 31 is a current signal of 4-20 mA.
Connect the actuator to the supply voltage, see wiring diagram.
Use terminal 4 at the power supply unit for permanent supply.
LED arrangement
Colour
green
LED
1
Check, whether the positioner has been connected correctly:
o Correct, if the LEDs 1, 2 and 4 light up green
o Wrong, if LED 3 lights up
Check the connections and pay attention to the polarity of the setpoint value input.
A setpoint value error has occurred if:
o LED 1 green is on
o LED 2 flashes or LED 2 is off
o LED 3 red is on
If the positioner is correctly connected: Do a learning run, see Chapter 7.5
"Performing a learning run".
The learning run is missing if:
o LED 1 green flashes
o LED 2 green is on
o LED 3 red is on
When changing from standard operation to other operating modes, the green LEDs
flash, depending on whether the SET or the ACTUAL value is suppressed.
Priority of the messages:
1) ACTUAL value
2) SET value
3) Control error
4) other operating modes
72
Accessories for electrical actuators
Terminal assignment positioner
199 190 101
27
SET value input current/ voltage
28
Output 12 V DC
29
SET value input ground
30
Position signalization signal
31
Position signalization ground
green
red
2
3
green
4