Accessories for electrical actuators
Connect the connector for the middle position to terminal 3.
15.4 Overview on activation
Actuator moves in
position
Open
CLOSED
Middle
* CCW - counterclockwise
** CW – clockwise, rotational direction seen from above on the indicator
Move actuator to position "OPEN" (CCW). For this, energize terminal 1.
Limit switch S1 is activated.
Move actuator to position "CLOSED" (CW). For this, energize terminal 2.
Limit switch S2 is activated.
Move actuator to middle position (CCW/CW). For this, energize terminal 3.
Switches S3/S4 are activated.
15.5 Setting the end positions
In order to set the opening angle from 90° to 180°:
Turn switching cam 2 of limit switch S2 by 90 ° anti-clockwise (seen from above).
Reconnect the device to the supply voltage.
Move the actuator into position "CLOSED" (terminal 2 energized).
Readjust cam 2 until the desired end position is reached (see position of the ball).
Replace the standard position indicator with the new 3-way position indicator.
Standard position indicator
Terminal energized
1
2
3
3
Activated switch(es)
S1
S2
S3
S4
e.g.
3-way position indicator
Middle position
Rotational direction
of the actuator
CCW*
CW**
CCW*
CW**
Ball with
T-port
89