Cycle counter

13 Cycle counter
Designation
Cycle counter

13.1 Exploded view

1
2
Fig. 25
1
BCD switch
2
LED

13.2 Function

This function allows setting a desired number of cycles. If a set number of cycles is
reached, a malfunction is reported. Via DIP switch 3 on the monitoring print, one can
preset if the actuator should keep moving in this case, or if it should move to its
security position and remain there.
Switch position
0
1
2
3
4
5
6
7
8
9
84
Technical data
Number of cycles
1
10,000
20,000
30,000
Delivery position EA42
40,000
Delivery position EA31
50,000
Delivery position EA21
60,000
70,000
80,000
90,000
Accessories for electrical actuators