Tab. 6: Electrical Output Parameters For The In4000 Standard Safety Switches - SICK Standard IN4000 Instrucciones De Servicio

Ocultar thumbs Ver también para Standard IN4000:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

en
Chapter 3
Tab. 6: Electrical
output parameters
for the IN4000
Standard
safety switches
WARNING
76
Product description
Logical "1"
Logical "0"
If the actuating element is outside the enable zone, the
output is switched off (Logical "0"; safe state).
Different timing behaviour, including continuous
Logical "1" is indicative of an error.
Cross-circuits are detected by the safety switch and
result in an error message (continuous Logical "1").
The pull-down current for the source of the PSDI must
not exceed 30 mA, as the safety switch cannot
process this current. It is then not possible to provide
an error message.
© SICK AG • Germany • All rights reserved
≥ 15 V
2 ... 15 mA
≥ 11 V
15 ... 30 mA
Output impedance typ.
27 Ohm
5V
Residual current 0 mA
Pull-down current typ.:
IN40-D0101K: 50 mA
IN40-D03 ..: 30 mA
IN40-D0202K: 30 mA
Operating Instructions
IN4000 Standard
8010934/ZWG9/2018-07-26
Subject to change without notice

Publicidad

Tabla de contenido
loading

Tabla de contenido