Do not use 90° curves.
Failure to comply with these requirements may prevent the correct operation of the unit
(please observe all of the instructions presented on the diagrams).
Insert operate with the combustion chamber in draught, which is why it is absolutely
necessary that they include a fume exhaust duct to adequately extract combustion
gases.
Side view of the installation without chimney, example of the inspection point
Fume duct material: the tubing to be used for this installation must consist of 0,5 mm thick
rigid stainless steel, with fitting bindings attaching the different sections and accessories.
Insulation: the fume ducts must be double-walled and insulated to make sure that fumes do
not cool down going outwards, which would cause an inadequate circulation and condensation
that might damage the unit.
Output T connection: always attach a "T-tube" with damper to the output of the unit.
Swing type check valve: always install this system to avoid fumes backflow.
Draught in the chimney: the figure below shows three standard diagrams, specifying the
adequate lengths and diameters. Any other type of installation must guarantee a draught of
12 Pa (0,12 mbars) measured when hot and at the maximum power.
EN // 91
USER'S MANUAL
EN