Unpacking and mechanical installation

Unpacking and examining the delivery
Size H1 ... H3
Do not lift the drive by the cover!
Mechanical installation

Before installation

Install the drive in an upright position with the cooling section facing a wall. Check the installation site according to the
requirements below. Refer to chapter Dimensions and weights in the Hardware manual for frame details.

Cabinet installation

The required distance between parallel units is five millimetres (0.2 in.) in installations without the front cover. The cooling
air entering the unit must not exceed +40 °C (+104 °F).
Preventing cooling air recirculation
Prevent air recirculation inside and outside the cabinet.
Hot area
Main airflow out
Cool area
Main airflow in
Size H4
Air baffle plates
BG_800_004_luft_b.ai
Size H5
Unit above another
max.+40°C
BG_800_003_luft_a.ai
Airflow
Lead the exhaust cooling air away from the unit above.
Distances see chapter Dimensions and weights.
A
A
BG_DCS_001_verpackung_a.ai
Air baffle plate
9
9