Connecting
3.2 Programming the Transmitter
3. Press <ENTER> key to select Pipe Class.
4. Press <Right Arrow> key. Press <Up/Down Arrow> keys to scroll to select desired Pipe
Size.
Note
Pre-programmed Pipe Size and relevant pipe parameters will appear in menu cells. Enter
dimensions manually if pre-programmed dimensions do not match application.
Note
The DN sizes listed in the [Select Pipe Size] menu option list are referenced to DIN Table
2448. After selecting pipe size, check pipe OD and wall thickness for correct dimensions.
5. Press <ENTER> key to save Pipe Size selection.
Select Liquid Class
1. Press <Left Arrow> key to select [Pipe Data] and then press <Down Arrow> key to select
[Application Data].
2. Press <Right Arrow> key to select [Liquid Class].
3. Press <Right Arrow> key again to select [Select Liquid]. Press <Right Arrow> key again.
4. Press <Up/Down Arrow> keys to scroll to desired liquid.
5. Press <ENTER> key to save selection.
20
Colon must appear first before Pipe Class can be selected.
Colon appears.
Select new liquid from option list.
FST020 IP65 NEMA 4X Quick Start
Operating Instructions, 08/2014, A5E03086489-AJ