ELECTRICAL INSTALLATION
Wiring Guidelines
Branch Circuit Protection
Integral solid state short circuit protection does not provide branch circuit protection. Branch circuit pro-
tection must be provided in accordance with the National Electrical Code and any additional local codes,
or the equivalent. Drive shall be protected by fuse or inverse-time circuit breaker only, rated 300 V, and
a maximum 300% of full load motor output current rating as noted below.
Input (Power) Wire and Fuse Sizing
Input
Model
Voltage
SubDrive 15
SubDrive 20
208/230
SubDrive 30
SubDrive 50
1 1
Based on a 3% voltage drop.
* * 90 °C Insulation only.
NOTE: Minimum breaker amps may vary from AIM Manual specifications because of VFD characteristics.
Output (Motor) Wire Sizing
Model
SubDrive 15
SubDrive 20
SubDrive 30
SubDrive 50
NOTE:
The use of 600 V minimum rated motor cable is required.
SubDrive models show cable lengths for highest power motor supported by each model. Refer to
the Franklin Electric AIM Manual when using a smaller motor.
Maximum allowable wire lengths are measured between the controller and motor.
Flat-jacketed submersible motor cable is recommended. All splices in the motor cable must be prop-
erly sealed with watertight shrink tubing. Use extreme caution to avoid damaging or compromising
the motor cable insulation during installation or service.
24
Fuse/
AWG Copper Wire Sizes, 75 °C Insulation, and Panel to Drive Cable Lengths (in feet)
Breaker
14
12
Amps
70*/
110/
15/15
85
135
20/20
-/85*
-
25/25
-
-
40/40
-
-
Motor Family
Horsepower
234 514 xxxx
1.5 (1.1 kW)
234 315 xxxx
2.0 (1.5 kW)
234 316 xxxx
3.0 (2.2 kW)
234 317 xxxx
5.0 (3.7 kW)
10
8
6
4
185/
280/
450/
710/
225
345
550
865
115/
180/
285/
450/
140
220
345
550
95*/
145/
235/
370/
115*
180
285
455
-/115* 150/
235/
-
185
290
AWG 600 V Copper Wire Sizes, 75 °C Insulation,
and Motor Cable Lengths (in feet)
14
420
670
320
510
240
390
-
230
3
2
1
880/
1160/
1465/
1075
1415
1795
555/
730/
925/
680
895
1130
460/
605/
765/
560
740
935
295/
385/
490/
360
470
600
12
10
8
1060
-
810
1000
620
990
370
590
1
1/0
2/0
610/
735/
745
895
6
4
-
-
-
-
-
-
920
-

Publicidad