OPERATION
Control Functions
Standard Constant Pressure Operation
D D r r i i v v e e R R u u n n n n i i n n g g
When the SubDrive Connect is controlling the motor and pump, the following infor-
mation will be shown on the illuminated display:
S S y y s s t t e e m m P P r r e e s s s s u u r r e e ( ( 1 1 ) ) : : When using a pressure transducer, the system displays
a numerical pressure reading (in PSI), followed by a "P" suffix to distinguish it
from motor speed. The "P" will steadily flash on and off when the drive is run-
ning the motor.
M M o o t t o o r r / / p p u u m m p p s s p p e e e e d d ( ( 2 2 ) ) : : When using a standard pressure sensor, the system
displays the current motor speed (in Hz).
S S y y s s t t e e m m I I d d l l e e
When the SubDrive Connect is powered on and idle (not pumping water), the fol-
lowing will be shown on the illuminated display:
S S y y s s t t e e m m P P r r e e s s s s u u r r e e : : When using a pressure transducer, the system displays the
resting pressure reading with the "P" steady (not flashing).
M M o o t t o o r r / / p p u u m m p p s s p p e e e e d d ( ( 3 3 ) ) : : When using a standard pressure sensor, the system
displays three dashes "– – –" indicating that the motor is not running.
F F a a u u l l t t D D e e t t e e c c t t ( ( 4 4 ) )
When a fault condition is detected in the system, the drive display will illuminate
red and the fault code will be displayed. Fault codes begin with "F" followed by a
one- or two-digit number. Refer to
information.
Moisture Sensor
If the system is equipped with a moisture sensor, the drive will stop pumping and
display Fault 25 when the sensor detects the presence of water.
If using Firmware version 2.1.0 or later, drive power must be cycled to clear the
fault.
If using Firmware prior to version 2.1.0, the fault will clear automatically when
moisture is no longer detected.
This does not replace the need for a pressure relief valve in the system.
The default setting for a Franklin Electric Moisture Sensor is F F a a u u l l t t w w i i t t h h H H i i g g h h . When
using a relay input from other external control devices, the setting may need to be
changed to F F a a u u l l t t w w i i t t h h L L o o w w .
Refer to
"Drawdown Feature (FE Connect App Only)" on page 34
"Diagnostic Fault Codes" on page 49
for more
for information about changing this setting.
OPERATION
Control Functions
37