Description of each instrument configuration parameter :
§ Display Contrast :
§ Alarm Settings :
500V
1000V
2500V
5000V
Adj. Voltage 1
Adj. Voltage 2
Adj. Voltage 3
Note : to return to the SET-UP menu, press the DISPLAY key
§ Adjustable Voltage 1, 2, 3
Adjustable Voltage 1
Adjustable Voltage 2
Adjustable Voltage 2
§ Timed Run (h : m)
§ Sample Time (m : s)
modification of display unit contrast
Default value
80
programming of measurement threshold values below which an
audible alarm is triggered.
Default value
< 500 kΩ
< 1,0 M Ω
< 2,5 M Ω
< 5 MΩ
< 50 k Ω
< 100 kΩ
< 250 k Ω
adjusted voltage : 3 different values can be predefined
Default value
50V
100V
250V
duration of test in "Timed run" mode
Default value
00 : 10 (h:m)
time interval between samples noted in Timed Run mode for
plotting R(t)
Default value
00 : 10 (m:s)
70
Range
0...255
Attention : the display unit is no longer
legible above 130
Range
30kΩ... 2TΩ
100k Ω ... 4T Ω
300k Ω ... 10T Ω
300kΩ... 10TΩ
10k Ω ... 10T Ω
10kΩ... 10TΩ
10k Ω ... 10T Ω
Range
40... 5100V
(in steps of 10V from 40V to 1000V
(in steps of 100V from 1000V to 5100V)
Range
00... 49 : 01... 59 (h:m)
Range
00... 59 : 05... 59 (m:s)