Descargar Imprimir esta página

Champion Global Power Equipment 100304 Manual De Instalación página 22

Ocultar thumbs Ver también para 100304:

Publicidad

Idiomas disponibles

Idiomas disponibles

HOME STANDBY GENERATOR- ALL aXis CONTROLLER
22-kW (Model 100304)
B
A
Two (2) 5 foot (1.5 m) lengths of 3/4 inch (1.9 cm) steel pipe
(supplied by the installer), are required to lift the HSB. Insert the
steel pipes through the lifting holes located near the HSB base in
the composite pad, on each end.
14-kW (Model 100515)
22-kW (Model 100304)
You may also lift the HSB using a properly rated strap, lift, hook
and hoist procedure attached to both steel lifting pipes, provided
that you use spreader bars to ensure that the belts, chains or
cables DO NOT touch/contact the HSB.
Once the HSB has been placed, check to make sure it is level. If it
isn't, make adjustments prior to installation procedures start.
MODELS
®
Installation Preparation
Improper installation can result in personal injury and damage
to the generator. It may also result in the warranty being
suspended or voided. All the instructions must be followed
including location clearances and pipe size.
Once Site Selection, Preparation and Placement has been
completed, you can proceed to Installation Preparation. Without
these in place you may encounter problems moving forward.
There are a number of key items that MUST be addressed prior
to the physical installation of the HSB. The installation of the HSB
must comply strictly with all applicable codes, standards and
regulations (NFPA 37, NFPA 54, NFPA 58, and NFPA 70).
Check and confirm that the aXis Controller
position. It is recommended to pull the control module fuse located
on the front panel and turn the circuit breaker to the OFF position.
Champion HSB units have been run and tested at the factory prior
to being shipped. They do not require any type of break-in period.
Check oil level, add oil if required. Add oil to full capacity as
stated in the specification section before starting the HSB.
Never operate the HSB with the engine oil level below the
"ADD" mark on the dipstick, doing so could damage the
engine. Check the oil level and add the appropriate viscosity
and amount indicated on the oil dipstick full line. The
recommended oil type for typical use is 5W-30 full synthetic
oil.
The following will be covered;
1. Fuel Requirements and Recommendations
2. Fuel Consumption
3. NG Pipe Sizing, flexible fuel line
4. LPG Vapor Pipe Sizing, flexible fuel line
5. Converting to LPG
6. Full Flow Shut Off Valve
7. Sediment Trap
8. Checking Pressure with a Manometer
9. Battery Requirements, Installation & Service
10. Wiring of the HSB
22
INSTALLATION
WARNING
is in the "OFF"
®
CAUTION

Publicidad

loading

Este manual también es adecuado para:

100515