HOME STANDBY GENERATOR- ALL aXis CONTROLLER
Recommended Battery Type
°F
-40
-4
°C
-40
-20
Ambient temperature
1. Place the batteries in the front right corner of the HSB
enclosure. Features on the floor of the enclosure locate
batteries. If replacing existing batteries, disconnect wiring
and remove old batteries.
2. Install positive cable first.
3. Install the battery series cable from the positive (+) terminal
of one battery to the negative (–) terminal of the other
battery. Always connect the positive (+) battery cable to the
generator (starter) first.
MODELS
®
350 CCA min
300 CCA min
32
68
104+
0
20
40+
U1L Battery
Post Style
to starter
To starter
Battery Series Cable
4. Dielectric grease should be applied on the battery
connections to aid in the prevention of corrosion.
5. Install both battery post covers.
6. Inspect, clean or re-grease battery connections every two
months.
22-kW (Model 100304)
Two (2) 12-volt Group 26 batteries with maximum overall
dimension (L x W x H) 8 3/16 x 6 13/16 x 7 3/4 inches / 208 x 173
x 197 mm with an Automotive (A) post or terminal configuration.
Purchase batteries locally.
The recommended battery type for typical use is 540 CCA (Cold
Cranking Amps). However, a 525 CCA battery shown in the
"Recommended Battery Type" chart may be used for typical use,
if in regularly warmer climates.
Alternatively, you may also use two (2) 12-volt Group 26R, but
both batteries must be 26R.
°F
-40
°C
-40
29
INSTALLATION
to ground
To ground
Recommended Battery Type
540 CCA min
525 CCA min
-4
32
68
104+
-20
0
20
40+
Ambient temperature
Automotive Post
Style
Group size 26

Publicidad

loading

Este manual también es adecuado para:

100515