HOME STANDBY GENERATOR- ALL aXis CONTROLLER
Wire Land
Function
Points
Wire land #1
L1
Wire land #2
N
Wire land #3
Ground
Wire land #4
+
Wire land #5
-
INPUT 120V - N/L
OUTPUT - CHARGER
The terminal block is prewired by the factory to the charger L1 and
N. A 120 VAC circuit must be installed for battery charging from
the ATS or another 120VAC circuit.
Wire Land
Function
Points
Wire land #1
L
Wire land #2
N
MODELS
®
The electrolyte is a diluted sulfuric acid that is harmful to the
skin and eyes. It is electrically conductive and corrosive.
The following procedures are to be observed:
Wire Color
R (Red)
W (white)
G (Green)
R (Red)
B (black)
Lead-acid batteries present a risk of fire because they
generate hydrogen gas.
The following procedures are to be followed:
10. WIRING Of THE HSB
Wire Sizing
Use a torque wrench to tighten conductors, being sure not to
overtighten, or damage to the switch base could occur. If not
tightened properly, a loose connection would result, causing
excess heat which could damage the switch base.
Wire Color
All installations must comply with National, State and Local codes.
R (Red)
It is the responsibility of the installer to perform an installation that
W (white)
will pass the final electrical inspection. Conductor wire sizes must
be adequate to handle the maximum current to which they will be
subjected. The installation must comply fully with all applicable
codes, standards, and regulations.
All power cables must enter the enclosure through the knockouts
provided. If not using knockouts, conduit entry into the enclosure
must be at or below knockouts to maintain the Type 3R rating.
33
CAUTION
1. Wear full eye protection and protective clothing,
2. Where electrolyte contacts the skin, wash it immediately
with water,
3. Where electrolyte contacts the eyes, flush thoroughly and
immediately with water and seek medical attention, and
40 Spilled electrolyte is to be washed down with an acid
neutralizing agent. A common practice is to use a solution
of one pound (500 grams) bicarbonate of soda to one
gallon (4 liters) of water. The bicarbonate of soda is to be
added until the evidence of reaction (foaming) has ceased.
The resulting liquid is to be flushed with water and the
area dried.
WARNING
1. DO NOT SMOKE when near batteries.
2. DO NOT cause flame or spark in battery area, and
3. Discharge static electricity from body before touching
batteries by first touching a grounded metal surface.
CAUTION
INSTALLATION