Descargar Imprimir esta página

Tripp-Lite PINV300SW-120 Manual Del Usuario página 16

Publicidad

Idiomas disponibles

Idiomas disponibles

Battery Connection
WARNING!
Make sure the inverter power switch is in the OFF position,
connect with included DC Wiring to the positive and negative
terminals. Though your Inverter is a high-efficiency converter of
electricity, its rated output capacity is limited by the length and
gauge of the cabling running from the battery to the unit. Use
the included cabling or the shortest length and largest diameter
cabling (recommended 5 AWG 16.77 mm²) with ring terminals
to fit your Inverter's DC Input terminals. Shorter and heavier
gauge cabling reduces DC voltage drop and allows for maximum
transfer of current. Your Inverter is capable of delivering peak
wattage at up to 200% of its rated continuous wattage output
for brief periods of time. Heavier gauge cabling should be used
when continuously operating heavy-draw equipment under these
conditions.
Recommended Cabling and Fusing
Model
PINV300SW-120
PINV600SW-120
PINV1000SW-120
PINV1500SW-120
Included Wire
Gauge and
Included
Quantity
Cable
(1x Red/1x Black)
Length
12 AWG
(3.33 mm²)
8 AWG
(8.37 mm²)
18.9 in.
(48 cm)
6 AWG
(13.3 mm²)
5 AWG
(16.77 mm²)
16
Ground
Wire Size
DC Fuse Size
and Length
(User-Supplied)
(Included)
60A
18 AWG
80A
(0.75 mm
39.4 in.
(100 cm)
200A
200A
)
2

Publicidad

loading

Este manual también es adecuado para: