7.7.3.1 Cable cross-section data for MGE motors
3 × 380-480 V, 50/60 Hz, Model K
Speed
Power P2
[rpm]
1450-2200
2900-4000
3 x 400-480 V, 50/60 Hz, Model K
Speed
Power P2
[rpm]
3500-4000
7.7.4 Conductors
Conductor types
Model K: Use stranded copper conductors only.
Conductor temperature ratings
Model K: Use minimum 75 °C copper conductors.
7.7.5 Three-phase connections
The cables in the terminal box must be as short as
possible. However, the separated protective-earth
conductor must be so long that it is the last one to be
disconnected in case the cable is inadvertently pulled
out of the cable entry.
To maintain the cURus mark, additional
requirements apply to the equipment. See
the appendix concerning installation in the
USA and Canada.
Model K: To avoid loose connections, ring terminals
must be used. Ensure that ring terminals are short
enough to stay within the terminal cover.
Check that the supply voltage and frequency
correspond to the values stated on the nameplate.
Supply voltage
[kW]
[V]
11
3 × 380-480
15
3 × 380-480
18.5
3 × 380-480
22
3 × 380-480
15
3 × 380-480
18.5
3 × 380-480
22
3 × 380-480
Supply voltage
[kW]
[V]
26
3 x 400-480
Cable cross-
Nominal
section
current
[A]
[mm
20.2 - 16.4
6
26.7 - 21.8
6
33.2 - 26.9
10
39.2 - 31.5
10
26.7 - 22
6
33 - 27.8
10
39.2 - 31.5
10
Cable cross-
Nominal
section
current
[A]
[mm
43.8 - 37.6
16
Power supply connection on a three-phase
product
L1
L2
L3
PE
Model K
Pos.
Description
L1
Phase 1
L2
Phase 2
L3
Phase 3
PE
Protective earth
Cable cross-
section
2
[AWG]
]
10
8
8
8
8
8
8
Cable cross-
section
2
[AWG]
]
6
11