To use the Rack Alignment template, complete these steps:
a. Place the Rack Alignment template over the left front vertical rack rail, then
move the bottom of the template to the location on the rack rail where the
bottom of the server will be located.
Mounting rail holes
b. Adjust the Rack Alignment template until the lower retainer screw opening is
centered on a hole in the rail.
c. Looking through the two slide bracket mounting holes on the Rack Alignment
template, locate and mark the two holes on the vertical rack rail that are most
visible through the template.
Use these two mounting holes to attach the slide assembly to the front rail. Mark
the corresponding holes on the right front vertical rack rail.
Guidelines for Installing Slide Assemblies
Caution – Stabilize the cabinet by extending its anti-tip legs or bolting the cabinet
securely to the floor.
If this is the first server you are installing into the cabinet, use holes 9 and 10 or 11
(this assumes that an AC power sequencer occupies holes 1 through 6 in the
bottom of the cabinet).
Install the slide assemblies into the lowest available position.
Install additional servers from the base up in the cabinet.
Chapter 1 Installing a Sun Fire V480 Server Into a 4-Post Cabinet