Select Liquid Class
1. Press the <Down Arrow> and scroll to [Application Data].
2. Press the <Right Arrow> to select [Liquid Class].
3. Press the <Right Arrow> again and scroll to desired liquid.
4. Press <ENT> to save selection.
Select Pipe Configuration
1. Scroll down to [Pipe Config] and press the <Right Arrow>.
2. Select a configuration that approximates the conditions upstream of your sensor
3. Press <ENT> to save selection.
4. Press the <Left Arrow> and return to the main menu.
FUS1010 IP65 NEMA 4X
Operating Instructions, 7/2010, A5E03086486-02
Select from list.
mounting location. (Refer to the definitions below.)
Use this menu cell to enter the number of pipe
diameters between the upstream configuration
and the Sensor installation.
Use this menu cell to select the pipe configuration
that most accurately represents the upstream pipe
condition.
Connecting
3.4 Programming the Transmitter
27