9
Applicable controls
REQUIREMENT
When you use this air conditioner for the first
time, it takes approx. 5 minutes until the remote
controller becomes available after power-on. This
is normal.
<When power is turned on for the first time
after installation>
It takes approx. 5 minutes until the remote
controller becomes available.
Approx. 5 minutes
"SETTING"
"SETTING"
Power on
flashes
goes out
<When power is turned on for the second (or
later) time>
It takes approx. 1 minute until the remote
controller becomes available.
Approx. 1 minutes
"SETTING"
"SETTING"
Power on
flashes
goes out
Normal settings were made when the indoor unit
was shipped from factory.
Change the indoor unit settings as required.
Use the wired remote controller to change the
settings.
* The settings cannot be changed using
the wireless remote controller, sub remote
controller, or remote-controller-less system
(for central remote controller only). Therefore,
install the wired remote controller to change the
settings.
33-EN
Basic procedure for changing
settings
Change the settings while the air conditioner is not
working. (Stop the air conditioner before making
settings.)
CAUTION
Set only the CODE No. shown in the following table:
Do NOT set any other CODE No.
Remote
If a CODE No. not listed is set, it may not be possible
controller is
available
to operate the air conditioner or other trouble with
the product may result.
* The displays appearing during the setting process
differ from the ones for previous remote controllers
(AMT21E, AMT31E). (There are more CODE No.)
Remote
controller is
available
4
6
1
5
2
1
Push and hold
button and "TEMP."
button simultaneously for 4 seconds or
more. After a while, the display fl ashes as
shown in the fi gure. Confi rm that the CODE
No. is [01].
If the CODE No. is not [01], push
to clear the display content, and repeat the
procedure from the beginning. (No operation of
the
remote controller is accepted for a while
after button is pushed.)
(While air conditioners are operated under the
group control, "ALL" is displayed first. When
is pushed, the indoor unit number
displayed following "ALL" is the header unit.)
(* Display content varies with
the indoor unit model.)
– 17 –
2
Each time
unit numbers in the control group change
cyclically. Select the indoor unit to change
settings for.
The fan of the selected unit runs and the louvers
start swinging. The indoor unit for change settings
can be confirmed.
3
Specify CODE No. [
/
buttons.
4
Select SET DATA [
/
buttons.
5
Push
button. When the display changes
from fl ashing to lit, the setup is completed.
To change settings of another indoor unit, repeat
from Procedure
To change other settings of the selected indoor
1
unit, repeat from Procedure
3
Use
button to clear the settings. To make
settings after
button was pushed, repeat from
2
Procedure
.
6
When settings have been completed, push
button to determine the settings.
When
button is pushed,
and then the display content disappears
and the air conditioner enters the normal
stop mode.
(While
is flashing, no operation of the
remote controller is accepted.)
button
External static pressure
button is pushed, indoor
settings
Set up a tap change based upon the external static
pressure of the duct to be connected.
To set up a tap change, follow to the basic operation
1
procedure (
Specify [5d] to the CODE No. in procedure
For the SET DATA of procedure
DATA of the external static pressure to be set up
from the following table.
<Change on wired remote controller>
] with "TEMP."
SET DATA
0000
0001
] with "TIME"
0002
0003
0004
0005
0006
2
.
The list above is when SW501-1 and SW501-2 is OFF.
3
.
flashes
2
3
4
5
6
).
3
.
4
, select a SET
External static pressure
40 Pa
Factory default
30 Pa
65 Pa
50 Pa
80 Pa
100 Pa
120 Pa
34-EN