Descargar Imprimir esta página

Toshiba RAV-GM901BTP-E Manual De Instalación página 24

Ocultar thumbs Ver también para RAV-GM901BTP-E:

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 118
Wired remote controller
1
When TEMPORARY button is pushed for 10
seconds or more, "Pi!" sound is heard and the
operation changes to test run. After approx.
3 minutes, a cooling operation starts forcedly.
Check cool air starts blowing. If the operation
does not start, check wiring again.
2
To stop a test operation, push TEMPORARY
button once again (Approx. 1 second).
Check wiring / piping of the indoor and outdoor
units in test run.
TEMPORARY button
45-EN
When a test run is not
performed properly
When a test run is not performed properly, refer
to the error code and the part to be checked on
"Troubleshooting".
When a test run is executed before installing the
external duct, a protection control may be activated
and lets the unit stop and the code P12 may be
displayed. (This is not due to a malfunction but to the
current control function of the DC motor in this unit.)
When a test run executed before installing the
external duct, select "Low" for the fan speed level or
cover the air discharge.
In addition, stop the operation before replacing the
High-effi ciency fi lter or opening the service panel.
After the test run, reset the circuit breaker of the
indoor unit.
– 23 –
11
Maintenance
<Daily maintenance>
4 Cleaning of the air filter
If
is displayed on the remote controller, maintain the air filter.
1
Push the
button to stop the operation, then
turn off the circuit breaker.
After the cooling or dry operation, the fan keeps
running for self-cleaning. Push the
twice to stop the operation.
1. Take out the air filter.
Slide and remove the filter as shown in the following figure:
WARNING
When the first filter comes out without connected to the other one, insert it once more to connect the two filters
together and pull out them as connected. Do not insert hands to take out the second filter. You may injure
yourself.
2. Cleaning with water or vacuum cleaner.
If dirt is heavy, clean the air filter by tepid water with neutral detergent or water.
After cleaning with water, dry the air filter sufficiently in a shade place.
3. Mount the air filter.
* Insert the filters into the direction which the arrows, carved on the filters, show. (2 filters are identical)
2
Turn on the circuit breaker, then push the
operation.
3
After cleaning, push
.
display disappears.
CAUTION
Do not start the air conditioner while leaving air filter removed.
Push the filter reset button. (
indication will be turn off.)
button
3
button on the remote controller to start the
1,2
46-EN

Publicidad

loading