5
1. Specify CODE No. [14] TEMP.
/
(CODE No. [14]: Group address)
2. Change the SET DATA from [0001] to [0002] TIME
/
buttons.
(SET DATA [Header unit: 0001] [Follower unit:
0002])
3. Push
button.
In this time, the setup finishes when the display
changes from flashing to lighting.
Indoor UNIT No. before setup change is displayed.
6
If there is other indoor unit to be changed,
2
5
repeat procedure
to
to change the
setup.
When the above setup has finished, push
to select the indoor UNIT No. before
change of setup, specify CODE No. [12],
[13], [14] in order with TEMP.
/
buttons, and then check the changed
contents.
Address change check Before change:
[3-3-1] → After change: [2-2-2]
Pushing
button clears the contents of which
setup was changed.
2
(In this case, procedure from
is repeated.)
Indoor UNIT No. before setup change is displayed.
41-EN
7
After check of the changed contents, push
button. (Setup is determined.) When
buttons.
button is pushed, the display disappears
and the status becomes the normal
stopped state. (When
button is pushed
the operation from the remote controller is
not accepted for approx. 1 minute.)
If the operation from the remote controller is
not accepted even 1 minute or more passed
after pushing
button, it is considered that the
address setup is incorrect.
In this case, the automatic address must be
again set up.
Therefore repeat procedure of the setup change
1
from the Procedure
.
– 21 –
To recognize the position of the
corresponding indoor unit though the
indoor UNIT No. is known
Check the position during operation stop.
(Stop operation of the unit.)
1,3
1
Push
+
buttons simultaneously for
4 seconds or more.
After a while, the display part flashes and
the display appears as shown below.
In this time, the position can be checked
because fan of the indoor unit operate.
For the group control, the indoor UNIT No. is
displayed as [
] and fans of all the indoor
units in the group control operate.
Check the displayed CODE No. is [01].
When the CODE No. is other than [01], push
button to clear the display and repeat procedure
from the first step.
(After pushing
button, operation of the
remote controller is not accepted for approx.
1 minute.)
(* Display changes according to
the model No. of indoor unit.)
2
In the group control, every time
button is pushed, the indoor UNIT No. in
the group control is displayed in order.
In this time, the position of the indoor unit
can be confirmed because only fan of the
selected indoor unit operate.
(For a group control, No. of the firstly displayed
indoor unit becomes the header unit.)
3
After confirmation, push
to the normal mode.
When
button is pushed, the display
disappears and the status becomes the
normal stopped state.
(When
button is pushed the operation from the
remote controller is not accepted for approx.
1 minute.)
1
2
button to return
42-EN