Descargar Imprimir esta página

Grundfos CU 362 Instrucciones De Instalación Y Funcionamiento página 12

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 163
5.1 CU 362
CU 362
Signal
Terminal
Float switch
Analog inputs
AI1
51
-
AI2
54
-
AI3
57
-
Digital inputs
DI1
10
Float switch
DI2
12
Float switch
DI3
14
Float switch
Digital outputs
DO1 (NO)
71
High-level alarm
DO1 (NC)
72
-
All alarms and
DO2 (NO)
74
warnings
DO2 (NC)
75
-
1)
See section Float switches.
Related information
5.3 Float switches
12
Description
The CU 362 is the "brain" of the Dedicated
Controls system and is mounted in the control
cabinet front.
The CU 362 can control and monitor up to six
Grundfos wastewater pumps. The pumps can
drain a pit using built-in draining algorithms. The
algorithms are based on a water level measured
by float switches or an analog level sensor.
Analog sensor
Level sensor
Flow sensor
User-defined sensor
1
1)
-
1)
-
1)
-
High-level alarm
-
All alarms and
warnings
-
Inputs and outputs
CU 362 inputs and outputs:
GENIbus communication (RS-485)
3 analog inputs for connection to sensors with
current (0-20 mA/4-20 mA) or voltage (0-10
V)
3 digital inputs
2 digital outputs, 240 VAC, 2 A
Connection to battery backup (UPS)
(optional)
Ethernet connection (VNC)
Connection to fieldbus CIM modules
(CIM: Communication Interface Module):
- CIM 200 (Modbus via RS-485)
- CIM 260 (Modbus and SMS via GSM/
GPRS)
- CIM 280 (Grundfos Utility Connect)
Level control and safety
Analog sensor and
Analog sensor and
safety float
mixer
switches
Level sensor
Level sensor
Flow sensor
Flow sensor
User-defined sensor
User-defined sensor
1
1
Dry-running float
-
switch
High-level float
-
switch
Overflow switch
-
High-level alarm
High-level alarm
-
-
All alarms and
All alarms and
warnings
warnings
-
-
Analog sensor,
mixer and safety
float switches
Level sensor
Flow sensor
User-defined sensor
1
Dry-running float
switch
High-level float
switch
Overflow switch
High-level alarm
-
All alarms and
warnings
-

Publicidad