Inputs for single-pole level probes
Input for minimum level float (connection between C and MAX)
C - MIN - MAX
Input for general enabling (connection between C and MAX)
Jumper C and MAX if not using this input
EN
Input for motor 1 activation
G/P1
When rotation operation is active, the first alternating motor will
start each time the input is opened and closed
Input for motor 2 activation
When rotation operation is active, each time the input is opened
G/P2
and closed it will start both motors regardless of the status of
G/P1 input
Input for motor 3 activation
When rotation operation is active, each time the input is opened
G/P3
and closed it will start three motors regardless of the status of
G/P1 and G/P2 input
Input for motor 4 activation
When rotation operation is active, each time the input is opened
G/P4
and closed it will start all motors regardless of the status of G/
P1, G/P2 and G/P3 input
G.A.
Input for alarm trigger
Cumulative alarm output with voltage-free contacts (resistive
load - 5A/250V) for:
- Probe level alarm
- G.A. input alarm
- Dry run motor alarm
OUT ALARM
- Motor overcurrent alarm
(NC - C - NO)
- Motor overtemperature alarm
- Voltage too low alarm
- Voltage too high alarm
- Sequence or missing phase alarm
- Max level alarm
BUZZ +/-
Alarm output, live (12Vcc/100mA)
SINGLE PHASE:
• L/S - Motor phase
• N/R - Motor idle
• AVV - Start with on board capacitor
OUT MOTOR
THREE PHASE:
• T1 (contactor) - Motor phase U
• T2 (contactor) - Motor phase V
• T3 (contactor) - Motor phase W
Earthing
10. EXPANSION INPUTS
RS485 expansion
Module for RS485 communication standard with MODBUS
A(-) – B(+)
protocol
Voltage-free contact expansion
Module for 6 digital outputs 300mA 35V max for the signalling of:
- O1: Motor 1 run
- O2: Motor 2 run
O1 – O6
- O3: Overcurrent protection for motor 1
- O4: Overcurrent protection for motor 2
- O5: GA active alarm
- O6: Probe/G.MIN active alarm
Probe input expansion for motor start
PRO-SL input module:
- C – MIN – MAX (on main board): motor 1 start
C – S1 ÷ S4
- C (expansion): common
- S1 – S2 (expansion): probe for motor 2 start control
- S3 – S4 (expansion): probe for max. level signalling
Probe input expansion for water seepage into oil chamber
RL-H2O input module:
- C: common (to be connected to earthing potential)
C – S4 ÷ S5
- S4 (expansion): probe for motor 1 control
- S5 (expansion): probe for motor 2 control
6
Buffer battery device expansion
PRODBT module for connection of 6V 1,2Ah buffer battery for
maintaining control of alarm float and for signalling mains power
supply failure
Bluetooth® expansion
Allows the panel to be connected to any device via Bluetooth®
to use the APP
11. SETTINGS MENU
To access the settings menu press and hold the SETUP key for
3 seconds.
DESCRIPTION OF PARAMETER
LANGUAGE
0=ITA/1=ENG/2=FRA/3=ESP/4=TED
DISPLAY BRIGHTNESS ON STANDBY
This parameter allows to enter the brightness setting applied
when the display is set to standby (wait 9 seconds for a preview).
KLIXON SELF-RESET
This parameter defines the automatic or manual reset of the
motor overtemperature alarm from Klixon
PUMP EXPANSION
This parameter defines whether the system provides the card for
the 3rd and 4th pump.
MINIMUM VOLTAGE
Set by default to -10%. (Altering operating limits beyond default
parameters will immediately render the warranty null and void).
MAXIMUM VOLTAGE
Set by default to +10%. (Altering operating limits beyond default
parameters will immediately render the warranty null and void).
MOTOR M1– M4 MAXIMUM CURRENT
This parameter allows the maximum current limit of the motor
to be set.
Enter the maximum current value, increasing it by 10-15% with
respect to the rated motor value.
Altering operating limits beyond the parameters stated on the
model data plate will immediately render the warranty null and
void.
MINIMUM CURRENT OR COS-FI CONTROL ACTIVATION
This parameter allows the dry run control to be enabled by read-
ing the absorbed motor current value or the cos-fi power factor.
MOTOR M1– M4 MINIMUM CURRENT
(If minimum current is enabled)
This parameter allows the MINIMUM motor current to be set
below which the motor must stop due to dry run. By setting the
current to 0, the minimum current dry run control is deactivated.
Enable this parameter only if no floats or probes are in use for
minimum level control.
MINIMUM COS-FI OF MOTOR M1 – M4 (if cos-fi is enabled)
This parameter allows the minimum motor cos-fi to be set below
which the motor must stop due to dry run.
PUMP ROTATION ACTIVATION
This parameter allows the pump changeover to be activated
every time the floats or pressure switches are triggered. In
addition, if the main pump is switched to thermal protection (over-
current), the second pump is enabled (the START/STOP function
is disabled with N).
AUTOMATIC RESET FOR DRY RUN
In the case of a dry run alarm (minimum cos-fi current) the panel
can attempt an automatic reset, programmable in minutes.
Four restart times can be set, whereby the system automatically
restarts after stopping.
AUTOMATIC RESET FOR DRY RUN TIME 1
First attempt to reset the dry run alarm (default: 5 minutes).
AUTOMATIC RESET FOR DRY RUN TIME 2
Second reset attempt counting from the previous reset attempt
(default: 10 minutes).
AUTOMATIC RESET FOR DRY RUN TIME 3
Third reset attempt counting from the previous reset attempt
(default: 20 minutes).
VALUE
0 - 4
0 - 9
AUTOMATIC
MANUAL
Y/N
207 (230)
360 (400)
253 (230)
440 (400)
1 - ... A
CURRENT
COS-FI
0 - ... A
0 - 1
Y or N
Y/N
1 - 240 Min
1 - 240 Min
1 - 240 Min