12.3 DIP-SWITCH 3 - Self-test
Motor self-test disabled
OFF
Motor self-test enabled
ON
EN
DIP-SWITCH 3 enables motor self-test.
In the OFF position, self-test is disabled.
In the ON position, self-test is enabled.
Self-test has a fixed, non-adjustable time and will enable the pump,
or pumps depending on the panel model, for 2 seconds every 48
hours.
A pump self-test can only be activated if the Automatic function of
the panel is enabled.
12.4 DIP-SWITCH 4 - Manual push or impulse key
Manual push key.
OFF
Manual impulse key.
ON
DIP-SWITCH 4 sets operation of the manual key.
In the OFF position, the manual key enables the motor by holding
the key down; when it is released, the motor stops.
In the ON position, the manual key enables the motor at the first
impulse and stops the motor at the next impulse.
13. RS485 9600 8N1 MODBUS ADDRESSES
ADDRESS
0x100
0x101
0x102
0x103
0x104
0x105
0x106
0x107
0x108
0x109
0x10A
0x10B
0x10C
0x10D
0x10E
0x10F
0x110
0x111
0x112
0x113
0x114
0x115
0x116
0x117
0x118
0x119
0x11A
0x11B
0x11C
0x11D
0x11E
0x11F
0x120
0x121
0x122
0x123
0x124
8
REGISTER
Card serial number
Firmware version in tenths
Display type
Power type
Number of pumps
Board 1 voltage value in V
Board 2 voltage value in V
Current value in A/10 Pump 1
Current value in A/10 Pump 2
Current value in A/10 Pump 3
Current value in A/10 Pump 4
Cosfi value in/100 Pump 1
Cosfi value in/100 Pump 2
Cosfi value in/100 Pump 3
Cosfi value in/100 Pump 4
Dip-Switch status
Current value set Trimmer M1 MIN
Current value set Trimmer M1 MAX
Current value set Trimmer M2 MIN
Current value set Trimmer M2 MAX
Value set Trimmer SENS.
Analog signal value in tenths
MASTER board input status
SLAVE board input status
MASTER board expansion status
SLAVE board expansion status
Output status
Alarm status 2
Alarm status 1
Alarm history 1
Alarm history 2
Alarm history 3
Alarm history 4
Alarm history 5
Alarm history 6
Alarm history 7
Alarm history 8
ADDRESS
0x125
0x126
0x127
0x128
0x129
0x12A
0x12B
0x12C
0x130
0x131
0x132
0x133
MANUAL command logic status
0x134
AUTOMATIC command logic status
0x135
Operating hours M1
0x136
Operating hours M2
0x137
Operating hours M3
0x138
Operating hours M4
0x139
0x13A
0x13B
0x13C
Standby display brightness
0x13D
Enabling EBARA name on panel
0x13E
Enabling panel name
0x13F
0x140
Maximum current setting in A/10
0x141
Alarm inhibition time at start-up in s/10
0x142
Pump start delay time in s/10
0x143
Pump shut-down delay time in s/10
0x144
Simultaneous pump activation delay time in s/10
0x145
Minimum current alarm delay time in s/10
0x146
Maximum current alarm delay time in s/10
0x147
High/low voltage alarm delay time in s/10
0x148
Pump current calibration 1
0x149
Pump current calibration 2
0x14A
Pump current calibration 3
0x14B
Pump current calibration 4
0x14C
Voltage board calibration 1
0x14D
Voltage board calibration 2
0x14E
Pump rotation enabling
0x14F
Alarm output enabling
0x150
Self-holding enabling
0x151
0x153
Control box operation
0x154
Minimum level alarm enabling
0x155
Min voltage alarm threshold
0x156
Max voltage alarm threshold
0x157
Max alarm threshold current pump 1 in A/10
0x158
Max alarm threshold current pump 2 in A/10
0x159
Max alarm threshold current pump 3 in A/10
0x15A
Max alarm threshold current pump 4 in A/10
0x15B
Cosfi/current alarm selection
0x15C
Min alarm threshold cosfi pump 1 in/100
0x15D
Min alarm threshold cosfi pump 2 in/100
0x15E
Min alarm threshold cosfi pump 3 in/100
0x15F
Min alarm threshold cosfi pump 4 in/100
0x160
Min alarm threshold pump current 1 in A/10
0x161
Min alarm threshold pump current 2 in A/10
0x162
Min alarm threshold pump current 3 in A/10
0x163
Min alarm threshold pump current 4 in A/10
0x164
Automatic reset for minimum current
0x165
Automatic reset time 1 in minutes
0x166
Automatic reset time 2 in minutes
REGISTER
Alarm history 9
Alarm history 10
Alarm history 11
Alarm history 12
Alarm history 13
Alarm history 14
Alarm history 15
Alarm history 16
Alarm reset 2
Alarm reset 1
Alarm history reset
Program to run
CT type
Language
Klixon self-reset
Probe sensitivity

Publicidad