Operation; Grounding Fastener; Generator Location; Starting The Engine - Briggs & Stratton GS2200 Manual De Instrucciones

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 18

operation

1
grounding Fastener Figure
The generator is provided with a grounding fastener (F). Local electrical codes may
require this to be connected to a suitable earth connection. The generator neutral
is floating, which means that the AC stator winding is isolated from the grounding
fastener and the AC receptacle ground pins. Electrical devices, such as RCD, requiring
a grounded neutral may not operate properly from this generator.
special requirements
There may be Federal, local codes, or ordinances that apply to the intended use of the
generator. Please consult a qualified electrician, electrical inspector, or the local agency
having jurisdiction:
• This generator has a floating neutral and is not for use on job sites requiring a
bonded neutral.
6

generator Location

Figure
warning POISONOUS GAS HAZARD. Engine exhaust contains carbon
monoxide, a poisonous gas that could kill you in minutes. You CANNOT
see it, smell it, or taste it. Even if you do not smell exhaust fumes, you
could still be exposed to carbon monoxide gas. If you start to feel sick,
dizzy or weak while using this product, shut it off and get to fresh air
RIGHT AWAY. See a doctor. You may have carbon monoxide poisoning.
• Operate this product ONLY outside far away from windows, doors and vents to
reduce the risk of carbon monoxide gas from accumulating and potentially being
drawn towards occupied spaces.
• Install battery-operated carbon monoxide alarms or plug-in carbon monoxide
alarms with battery back-up according to the manufacturer's instructions. Smoke
alarms cannot detect carbon monoxide gas.
• DO NOT run this product inside homes, garages, basements, crawlspaces,
sheds, or other partially-enclosed spaces even if using fans or opening doors and
windows for ventilation. Carbon monoxide can quickly build up in these spaces
and can linger for hours, even after the product has shut off.
• ALWAYS place this product downwind and point the engine exhaust away from
occupied spaces.
8
7
1
starting the engine Figure
NOTICE This engine was shipped without oil. Before you start the engine, make sure
you add oil according to the instructions in this manual. If you start the engine without
oil, it will be damaged beyond repair and will not be covered under warranty.
NOTICE Before you start the engine, make sure that all electrical devices are
disconnected from the generator outlets.
1. Make sure unit is on a flat, level surface.
NOTICE Failure to start and operate the unit on a flat, level surface will cause the unit
not to start or shut down during operation.
2. Turn fuel valve (P) to on position (i).
3. Pull choke control (c) out to close choke (
4A. For electric starting, turn and hold key in start switch (a) to start (
until generator starts. To prolong the life of starter components, DO NOT hold key
in start (
) position for more than 15 seconds, and pause for at least 1 minute
between starting attempts.
If engine starts, proceed to step 6.
If engine fails to start, proceed to step 5.
NOTICE If battery is discharged, use manual starting instructions.
warning Starter cord kickback (rapid retraction) will pull hand and arm
toward engine faster than you can let go which could cause broken
bones, fractures, bruises, or sprains resulting in serious injury.
• When starting engine, pull cord slowly until resistance is felt and then pull rapidly
to avoid kickback.
• NEVER start or stop engine with electrical devices plugged in and turned on.
4B. For manual starting, turn key in start switch to run (i) position, grasp recoil
handle (n) and pull slowly until slight resistance is felt. Then pull rapidly one
time only to start engine.
If engine starts, proceed to step 6.
If engine fails to start, proceed to step 5.
5. Push in the choke handle half way, turn key in start switch to run (i) position
and pull recoil handle twice or turn and hold key in start switch to start (
position as described in step 4A.
If engine fails to start, repeat steps 3 thru 4.
6. Open the choke gradually as the engine warms up by pushing in on the choke
handle.
NOTICE If engine floods, push choke handle all the way in and crank until engine starts.
NOTICE If engine starts after 3 pulls but fails to run, or if unit shuts down during
operation, make sure unit is on a level surface and check for proper oil level in
crankcase. This unit is equipped with a low oil protection device. If so, oil must be at
proper level for engine to start.
warning Exhaust heat/gases could ignite combustibles, structures or
damage fuel tank causing a fire, resulting in death, serious
injury and/or property damage.
Contact with muffler area could cause burns resulting in
serious injury.
• DO NOT touch hot parts and AVOID hot exhaust gases.
• Allow equipment to cool before touching.
• Keep at least 1.5 m (5 ft.) of clearance on all sides of generator including overhead.
• Contact the original equipment manufacturer, retailer, or dealer to obtain a
spark arrester designed for the exhaust system installed on this engine.
• Replacement parts must be the same and installed in the same position as
the original parts.
8
).
) position
)
Briggsandstratton.coM

Publicidad

Tabla de contenido

Solución de problemas

loading

Este manual también es adecuado para:

Gs3500Gs5500Gs5500e

Tabla de contenido