13. MAINTENANCE
13.1. CONTROLS
It is user responsibility to take charge of maintaining integrity and efficiency of the GIR/IBC and its devices and equipment, in particular
periodically check:
– the perfect sealing of the GIR/IBC, paying the utmost attention to possible loss or leakage of the liquid at the inlet, drainage of the pipe
fittings of draught and delivery, as well as of the tap.
– the good condition of the inscriptions on the Cabinet identifying the material (e.g. "UN1202") and, if deteriorated, replace them with new ones.
– the ADR danger labels are in good condition and, if damaged, replace them with new ones of the same type.
– the good state of pictograms warning stickers for lifting points and, if damaged, replace them with new ones of the same type and in the
same exact position. .
User is responsible for maintaining healthy and efficient everything concerning the emptying device and its electrical system.
In particular must be checked:
– Daily:
·
Surface state of the rubber tube (free from cracks or abrasions)
· Perfect sealing of the suction and discharge piping fittings
(check with electric pump in bypass mode function).
– Weekly:
·
the good state of the plate with the safety warnings
·
the electrical connections are in good condition, and the insulation of power cables by replacing any one damaged.
·
check the status of the equipotential grounding cable.
Before any parts replacement:
- Disconnect the machine from the power source
- Discharge the delivery pressure by exerting a short pulse of residual delivery with the gun.
13.2. CLEANING
The GIR/IBC and its emptying device should be kept clean both by external agents (dirt, dust, etc.), and from accidental spills of dangerous
materials during fills, flushes, losses.
For the cleaning of metal parts, electric cables and plastics in general use non-corrosive products, preferring neutral or slightly alkaline
degreasing products. Steam systems can be used (steamer), provided that the jet is not directed against parts of the electrical system or
against the labels and/or adhesive plates applied on the body of the GIR/IBC and the metal frame of the emptying device.
13.3. TAMPERING
In addition to the provisions in section 13.5, for no reason it is possible to modify GIR/IBC regarding electric discharge device character-
istics; in particular
It is strictly prohibited to:
Replace original equipment with other components other than the original ones, without manufacturer's warranty as
regards pressure resistance.
Replace the plug-socket system with a permanent connection or connection systems not effectively combating flying
glitter during live connection.
Change the pressure-relief device.
Prepare additional venting devices.
– Tamper with/remove the equipotentiality cable
13.4. ACCIDENTS
In case of accidental damage to its containment and/or protection structure, and/or its devices and equipment, the GIR/IBC will be subject-
ed to extraordinary revision by the entity in charge with issuing a new report of commissioning, from which date the 30 months for further
review will be counted again, without prejudice to the 60-month maximum period of use (see § 3.5).
13.5. SPARE PARTS
Any modification or replacement of parts of the housing, as a result of damage, accident or tampering, is allowed only at EMILIANA
SERBATOI srl establishments or in centres authorised by it, as the operation is configured as "reconditioning" and as such involves the
re-issuance of the commissioning report (see § 3.5).
14. PERSONAL PROTECTION EQUIPMENT
14.1. EQUIPMENT OF THE STAFF ONBOARD
Even in the case of ADR partial exemption, while not explicitly set, it is still desirable to have appropriate personal protective equipment
(PPE), also in order to comply with current legislation and legislation on health and safety at work (Decree Law 81/08 - Lgs. D. 106/2009):
– n° 1 pair of work gloves in accordance to EN 374
– n° 1 pair of slip resistant boots
– eye protection glasses
– pure water in case of eyes contamination.