Output Configuration; Diagnostics Suppression - Balluff BML SL1-ALZ-ZZ Serie Manual De Instrucciones

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

BML SL1-ALZ _-_ _ ZZ- _ _ _ _ - _ _ _ _
Absolute Magnetically Coded Position Measuring System
7
IO-Link Smart Sensor profile Ed. 2 (BML SL1-ALZ1-UE/MZZ-_U1L-...) (continued)
Teach-In
1. Use Tl Select to select the desired switching signal (1
to 4).
2. Move the head to the turn-on position.
3. Execute the Single Value Teach SP1 (0x41) command
(see System commands on page 27).
4. Move the head to the turn-off position.
5. Execute the Single Value Teach SP2 (0x42) command
(see System commands on page 27).
You can check your steps using the Teach-In
Result parameter.
7.5.3

Output configuration

Both BML outputs can be configured.
Index
Subindex
Output Type
1
0x00B4 (180)
2
Tab. 7-10: Output configuration
7.5.4

Diagnostics suppression

If diagnostics functions cause problems in the application,
these functions can be suppressed.
For diagnostic events implemented in the BML see Event
list on page 35.
Index
Subindex
Diagnosis
1
Suppression
Configuration
0x00F8 (248)
2
Tab. 7-11: Diagnostics suppression
www.balluff.com
Name
Size
Out 1
1 byte
Out 2
1 byte
Name
Size
Suppression Level
1 byte
PD Invalid Suppression
1 byte
Access
Values
Read/Write 0 = Disabled
1 = PNP (default)
2 = NPN
3 = Push-Pull
Read/Write 0 = Disabled
1 = PNP (default)
2 = NPN
3 = Push-Pull
Access
Values
Read/Write 0 = All events active (default)
1 = Messages suppressed
2 = Messages and warnings suppressed
3 = All events suppressed
Read/Write 0 = PD Invalid active
1 = PD Invalid suppressed
english
31