Malfunctions
This section lists a number of malfunctions which may occur.
SURGE OVERLOAD ALARM
SAFETY EDGE ALARM
ENCODER ALARM
PHOTOCELL ALARM/SAFETY EDGE
LIMIT SWITCH ALARM
After eliminating the cause of the alarm, to eliminate the error message you must give an opening or closing command from the limit
switch, or press "MENU" ( ) button.
Press "UP" ( ) button to read the following parameters on display.
42
SO
Barrier stopped during opening
SC
Barrier stopped during closure
F1
Photocell 1 tripped
F2
Photocell 2 tripped
ALI
Re-alignment procedure
oP
Barrier open without automatic reclosure
OPD
Barrier in partial opening mode
Pe
Barrier in partial opening position without automatic reclosure
Barrier open with timed reclosure
-tC
Flashing dash counting in progress
Dash replaced by figures 0..9 countdown (last 10s)
Barrier in partial opening position with timed reclosure
-tP
Flashing dash counting in progress
Dash replaced by figures 0..9 countdown (last 10s)
L--
Learning stopped due to activation of safety device or motor reverse
LOP
Learning on M1 opening
LCL
Learning on M1 closing
SOP
Point of M1 deceleration on opening (only during stroke learning)
SCL
Point of M1 deceleration on closing (only during stroke learning)
DESCRIPTION
During the programming phase
Motor 1 obstacle detected
Photocell 1 tripped / Photocell 2 tripped
Safety edge tripped
Phototest error detected
Line overload in flash / courtesy lights / electric lock / barrier light
The motor's current drawdown has increased very quickly
1. The barrier has hit an obstacle (M1)
2. There is friction on the leaf of M1
The control unit has received a signal from the safety edge
1. The safety edge has been pressed.
2. The safety edge is not connected correctly
Encoder do not respond
1. Check the encoder connection
2. Check that the encoder is operating correctly
Phototest fail outcome
1. Check the photocell and the safety edge connections
2. Check that the photocells and the safety edge are operating correctly
Limit switch fail
1. Check the limit switch connection
2. Check that the limit switch are operating correctly
KEY TO MAIN CONTROL
FLASHING LIGHT AND KEY
LEDS CONTROL UNIT
2 quick flashes + pause + 1 flash
4 quick flashes + pause, 3 times
2 quick flashes + pause, 3 times
5 quick flashes + pause, 3 times
3 quick flashes + pause, 3 times
6 quick flashes + pause, 3 times