Device designs
2
Device designs
Important (Notice)
An additional document with Ex safety instructions is available for measuring systems that are
used in explosion hazardous areas. As a result, it is crucial that the specifications and data it
lists are also observed.
2.1.1
Model with compact design
The transmitter and the flowmeter sensor form a single mechanical entity.
Fig. 1
2.1.2
Model with remount mount design
The transmitter is mounted in a separate location from the flowmeter sensor. The electrical
connection between the transmitter and the sensor is provided by a signal cable.
Without a pre-amplifier, the maximum permissible signal cable length is 50 m (164 ft) with a
minimum conductivity of 5 µS/cm.
With a pre-amplifier, the maximum permissible signal cable length is 200 m (656 ft).
Fig. 2
10 - EN
ProcessMaster
ProcessMaster
FEX300, FEX500
HygienicMaster
HygienicMaster
CI/FEX300/FEX500-X1