Appendix 1: - P1 Communications Set-up and Point Map
Parameter Set-up: The Table below lists the Parameters and the setting values required for proper P1 FLN
communication and control
Parameter number/name
P0003: User access level
Set to 3 to allow access to required parameters.
P2040: CB telegram off time
Set to 0 to tell the drive to start looking for communication via setting of
P2041.
P2041(index 0): CB parameter
Set to "1 Set to "0" for FLN (P1) control (set to "1" for FLN (N2) control).
P0918: CB address
Set to "1-99" for addressing of the device.
P0700 (index 0)
Set to 6 tells the SED2 to look for a start command from P1 in the auto mode.
P1000 (index 0)
Set to 6 tells the SED2 to look for its speed source from P1 in the auto mode.
Point Number
Point
Descriptor
Factory Default
(drive
Type
(SI Units)
parameter)
CTLR ADDRESS
01
LAO
99
02
LAO
APPLICATION
2722
(03)
LAI
FREQ OUTPUT
0
(05)
LAI
SPEED
0
(06)
LAI
CURRENT
0
TORQUE
(07)
LAI
0
ACTUAL POWER
(08)
LAI
0
TOTAL KWH
(09)
LAI
0
(13)
LAI
DC BUS VOLT
0
(14)
LAI
REFERENCE
0
(16)
LAI
RATED PWR
0
(17)
LAI
OUTPUT VOLTS
0
20
LAO
OVRD TIME
1
FWD.REV
(21)
LDI
FWD
CMD FWD.REV
(22)
LDO
FWD
(23)
LDI
STOP.RUN
STOP
CMD STP.STRT
(24)
LDO
STOP
(25)
LDI
AT MAX FREQ
NO
(26)
LDI
CONTROL MODE
SERIAL
(27)
LDI
ENABLED
OFF
(28)
LDI
READY TO RUN
OFF
(29)
LDO
DAY.NIGHT
DAY
CURRENT LIM
30
LAO
1400
ACCEL TIME 1
31
LAO
500
32
LAO
DECEL TIME 1
500
34
LDO
SEL HND.AUTO
AUTO
(35)
LDO
RUN ENABLE
ENABLE
40
LDO
DIGITAL OUT 1
OFF
41
LDO
DIGITAL OUT 2
OFF
ANALOG IN 1
(45)
LAI
0
ANALOG IN 2
(46)
LAI
0
ANALOG OUT 1
(47)
LAI
0
ANALOG OUT 2
(48)
LAI
0
(51)
LAO
FREQ REF
0
(52)
LA1
FREQ ACTUAL
0
53
LAO
FREQ MAX
2450
CM1G5192X
Value
P1 Point Map
Engr. Units
Slope
Intercept
On Text
Off Text
(SI Units)
(SI Units)
(SI Units)
1
0
1
0
HZ
.04
-650
RPM
1
-16250
A
0.5
0
NM
.02
-3250
HP/KW
.01
0
KWH
1
0
V
1
0
HZ
.04
-650
HP/KW
.01
0
V
1
0
HRS
1
0
REV
FWD
1
0
REV
FWD
1
0
1
0
RUN
STOP
START
STOP
1
0
1
0
MAX
NO
1
0
SERIAL
LOCAL
1
0
ENABLED
OFF
1
0
READY
OFF
1
0
NIGHT
DAY
PCT
.1
10
SEC
.02
0
SEC
.02
0
1
0
AUTO
HAND
1
0
ENABLE
OFF
1
0
ON
OFF
1
0
ON
OFF
PCT
.1
-300
PCT
.1
-300
PCT
.1
-100
PCT
.1
-100
PCT
0.0061
0
PCT
0.0122
-100
HZ
0.2
1
Point Number
Point
Descriptor
Factory Default
(drive
Type
(SI Units)
parameter)
PID SETP REF
(55)
LAO
PID SETP OUT
(56)
LAI
57
LAO
PID UP LMT
58
LAO
PID LO LMT
(59)
LAI
PID OUTPUT
(60)
LAI
PI FEEDBACK
61
LAI
P GAIN
I GAIN
62
LAI
D GAIN
63
LAI
ENABLE PID
64
LDO
66
LAI
FEEDBK GAIN
68
LAI
LOW PASS
(71)
LDI
DIGITAL IN 1
(72)
LDI
DIGITAL IN 2
(73)
LDI
DIGITAL IN 3
(74)
LDI
DIGITAL IN 4
DIGITAL IN 5
(75)
LDI
DIGITAL IN 6
(76)
LDI
80
LAO
WDOG TIME
83
LAI
INVERTER VER
84
LAI
DRIVE MODEL
(90)
LAI
LAST FAULT
(91)
LAI
1
ST
FAULT
2
ST
FAULT
(92)
LAI
3
FAULT
(93)
LAI
ST
OKFAULT
(94)
LDI
(95)
LDO
FAULT ACK
(96)
LDI
WARNING
(97)
LAI
LAST WARNING
(99)
LAO
ERROR STATUS
1.
Points not listed are not used in this application.
2.
A single value in a column means that the value is the same in English units and in
SI units.
3.
Point numbers that appear in brackets { } may be unbundled at the field panel.
10
Engr. Units
Slope
Intercept
On Text
(SI Units)
(SI Units)
(SI Units)
PCT
8602
0.0244
-200
PCT
0
0.0122
-100
12288
PCT
0.0244
-200
8192
PCT
0.0244
-200
0
PCT
0.0122
-100
0
PCT
0.0122
-100
0
PCT
0.002
0
PCT
0
2
0
PCT
0
2
0
ON
0
1
0
0
PCT
0.02
0
0
0.01
0
0
1
0
ON
0
1
0
ON
0
1
0
ON
0
1
0
ON
ON
0
1
0
ON
0
1
0
0
1
0
0
0.01
0
0
1
0
0
1
0
0
1
0
0
1
0
0
1
0
FAULT
0
1
0
0
1
0
ON
0
1
0
WARN
0
1
0
0
1
0
Off Text
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OK
OFF
OK

Publicidad

loading