74
AVENTICS | Bus Coupler AES/Valve Driver AV, PROFINET IO | R412018140–BAL–001–AG
About This Product
UL
UA
IO/DIAG
RUN/BF
L/A 1
L/A 2
S1
S2
4.1.2
LED
The bus coupler has 6 LEDs.
The table below describes the functions of the LEDs. For a comprehensive description of the LEDs,
see section 11 "LED Diagnosis on the Bus Coupler" on page 94.
Table 8:
Meaning of the LEDs in normal mode
14
Designation
Function
15
UL (14)
Monitors electronics power supply
16
UA (15)
Monitors the actuator voltage
IO/DIAG (16)
Monitors diagnostic reporting from all modules
17
RUN/BF (17)
Monitors data exchange
18
L/A 1 (18)
Connection with Ethernet device on fieldbus
19
connection X7E1
L/A 2 (19)
Connection with Ethernet device on fieldbus
connection X7E2
4.1.3
Address switch
Fig. 2:
Location of address switches S1 and S2
The two rotary switches S1 and S2 for manual valve system name assignment are located
underneath the window (3).
Switch S1: The higher digit of the hex value in the name is set at switch S1. Switch S1 is labeled
using the hexadecimal system from 0 to F.
Switch S2: The lower digit of the hex value in the name is set at switch S2. Switch S2 is labeled
using the hexadecimal system from 0 to F.
A comprehensive description of addressing can be found in section 9 "Presettings on the Bus
Coupler" on page 88.
Status in normal mode
Illuminated green
Illuminated green
Illuminated green
Illuminated green
Illuminated in green and simultaneously
flashes quickly in yellow
Illuminated in green and simultaneously
flashes quickly in yellow
S1
S1
S2
S2
3