AVENTICS | Bus Coupler AES/Valve Driver AV, PROFINET IO | R412018140–BAL–001–AG
Presettings on the Bus Coupler
Setting the rotary switch
to PROFINET IO function
Assigning name, IP address, and
subnet mask
3. Reconnect the power supply UL.
The system is initialized and the name on the bus coupler is set to AES-D-BC-PNIO-XX. "XX"
corresponds to the switch setting. Name assignment with PROFINET IO functions is deactivated.
Table 19 provides some naming examples.
Table 19:
Naming examples
S1 switch position,
Higher value digit
(hexadecimal label)
0
0
0
...
f
f
9.3.2

Name assignment with PROFINET IO functions

1. Disconnect the bus coupler from the power supply UL before changing the positions of switches
S1 and S2.
2. Once you have done this, you can set the name to 0x00.
After the bus coupler is restarted, PROFINET IO functions are active.
After you have set the rotary switch on the bus coupler to PROFINET IO function, you can assign
it a name, an IP address, and the subnet mask.
The procedure to assign a name, an IP address, and the subnet mask to the bus coupler
depends on the PLC configuration program. Please see the operating instructions
for the program for more information.
The following example is based on the SIMATIC software from Siemens. The PLC configuration can
also be done using a different PLC configuration program.
Danger of injury if changes are made to the settings during operation.
Uncontrolled movement of the actuators is possible!
Never change the settings during operation.
To edit the correct device:
1. First look for the participant that you would like to edit.
In this example, it is the AES series bus coupler.
The bus coupler is shown with the IP address 0.0.0.0 (or an already-configured address).
S2 switch position,
Lower value digit
(hexadecimal label)
0
1
2
...
e
f
CAUTION
Name
0 (name assignment with PROFINET IO
functions)
AES-D-BC-PNIO-01
AES-D-BC-PNIO-02
...
AES-D-BC-PNIO-FE
255 (reserved)