AVENTICS | Bus Coupler AES/Valve Driver AV, PROFINET IO | R412018140–BAL–001–AG

LED Diagnosis on the Bus Coupler

Reading the diagnostic display
on the bus coupler
UL
UA
IO/DIAG
RUN/BF
L/A 1
L/A 2
11 LED Diagnosis on the Bus Coupler
The bus coupler monitors the power supplies for the electronic components and actuator control.
If they exceed or fall below a set threshold, an error signal will be generated and reported
to the controller. In addition, the status is displayed by the diagnostic LEDs.
The LEDs on the top of the bus coupler reflect the messages listed in Table 21.
Before commissioning and during operation, regularly check the bus coupler functions
by reading the LEDs.
Table 21:
Meaning of the diagnostic LEDs
14
Designation
Color
15
UL (14)
Green
16
Red
17
18
Red
19
Green/red
UA (15)
Green
Red
Red
IO/DIAG (16)
Green
Red/green
Red
Red
RUN/BF (17)
Green
Green
Red
Red
Green/red
L/A 1 (18)
Green
Yellow
Green/
yellow
L/A 2 (19)
Green
Yellow
Green/
yellow
State
Meaning
Illuminated
The electronics supply voltage is greater than the lower
tolerance limit (18 V DC).
Flashes
The electronics supply voltage is less than the lower tolerance
limit (18 V DC) and greater than 10 V DC.
Illuminated
The electronics supply voltage is less than 10 V DC.
Off
The electronics supply voltage is significantly less than
10 V DC (limit not defined).
Illuminated
Actuator voltage exceeds the lower tolerance limit (21.6 V DC).
Flashes
The actuator voltage is less than the lower tolerance limit
(21.6 V DC) and greater than UA-OFF.
Illuminated
The actuator voltage is less than UA-OFF.
Illuminated
The configuration is OK and the backplane is working
perfectly.
Flashes
The master configuration does not match the hardware of the
connected slave (too many, too few, or wrong modules have
been configured)
Illuminated
Diagnostic message from module present
Flashes
Valve unit incorrectly configured or backplane function error
Illuminated
The bus coupler exchanges cyclical data with the controller.
Flashes
Waiting to establish communication with the controller
Flashes
Communication was disrupted (no communication with
the master)
Illuminated
Severe network problems, IP address assigned twice
Off
Waiting for connection to the network (at least one link must
be established)
Illuminated
The physical connection between the bus coupler and
network has been detected (link established).
Flashes
Data packets received (flashes for each data packet received)
quickly
Off
The bus coupler does not have a physical connection with
the network.
Illuminated
The physical connection between the bus coupler and
network has been detected (link established).
Flashes
Data packets received (flashes for each data packet received)
quickly
Off
The bus coupler does not have a physical connection with
the network.