Installation and Connection
3.2.4 Grounding Connections
DANGER!
The inverter must be connected to a protection grounding (PE).
Use grounding wiring with a gauge at least equal to that indicated in
B.1 on page
The maximum tightening torque of the grounding connections is of 1.7 N.m
(15 lbf.in).
Connect the grounding points of the inverter to a specific grounding rod, or
specific grounding point or to the general grounding point (resistance ≤ 10 Ω).
The neuter conductor that powers up the inverter must be solidly grounded.
however, this conductor must not be used to ground the inverter.
Do not share the grounding wiring with other equipment that operate with
high currents (e.g. high power motors, soldering machines, etc.).